TLP150N-99S12J Datasheet, PDF (1/4 Pages) Emerson Network Power – Single output | |||
|
POWER
Data Sheet
Total Power: 150 Watt
Input Voltage: 85 - 264 Vac
# of Outputs: Single
SPECIAL FEATURES
ÂÂ 150 W on main channel with only
200 LFM
ÂÂ Low profile fits 1U applications
ÂÂ Active PFC and EN61000-3-2
compliant
ÂÂ Integrated control and monitoring
features
ÂÂ Overcurrent, overvoltage and
overtemperature protection
ÂÂ Compliance to EN55022-B
conducted noise standard
ÂÂ 12 V fan output
ÂÂ 5 V standby output (optional)
ÂÂ RoHS compliant
ÂÂ Two year warranty
SAFETY
ÂÂ TUV EN60601-1/IEC60601-1
ÂÂ VDE CB Certificate and Report
ÂÂ UL 60950-1
TLP150 Medical Series
Single Output
Electrical Specifications
Input
Input voltage range
Universal Input
Input frequency range
Input surge current
264 Vac (cold start)
Safety ground leakage
current
264 Vac, 50 Hz
Input current
120 Vac @ 150 W
230 Vac @ 150 W
Input fuse:
UL/IEC127
Output
Adjustment range
Total regulation (line and
load)
Main output
Auxiliary outputs
Fan output
Turn-on delay
@120 Vac Input
Transient response
Main output
25% to 75%
step at 0.5 A/µs
Temperature coefficient
Overvoltage protection
Main outputs
Short circuit protection
Current limited
Minimum output current Singles
Fan voltage output
See Note 9
Standby output
See Note 9
85 - 264 Vac
47 - 63 Hz
40 A max.
150 μA
1.8 A rms
0.8 A rms
T 3.15 A, 250 Vac
± 10%
± 3%
± 5%
± 10%
2.0 s max.
5%
max. dev., 1 ms max.
recovery to 1%
±0.02%/°C
125%, ± 5%
Continuous
0A
12 V @ 0.5 A
5 V @ 1.0 A
|
▷ |