English
Language : 

BXB100-24S12FLTJ Datasheet, PDF (1/3 Pages) Artesyn Technologies – Total Power: 66 - 100 W
POWER
Data Sheet
BXB Series
66 - 100 Watts
Total Power: 66 - 100 W
Input Voltage: 18 - 36 V
36 - 75 V
# of Outputs: Single
SPECIAL FEATURES
ƒƒ Industry standard footprint
ƒƒ High power density (36.5 W/in3)
ƒƒ MTBF >1.4 million hours (Bellcore 332)
ƒƒ Input voltage to ETS300-132-2
ƒƒ Adjustable output voltage
ƒƒ No minimum load required
ƒƒ Separate case ground pin
ƒƒ Undervoltage lockout (UVLO)
ƒƒ UL, VDE and CSA safety approvals
ƒƒ Two year warranty
Electric
Input
Input voltage range
Input current
SAFETY
ƒƒ VDE0805/EN60950/IEC950
ƒƒ UL1950
ƒƒ CSA C22.2 No. 950
Input current (max.) (See Note 4)
Input reflected ripple
Active low remote ON/OFF
(See Note 7)
Undervoltage lockout
Start-up time
(See Note 8)
Output
Voltage adjustability
Setpoint accuracy
Line regulation
Load regulation
Minimum load
Overshoot
Undershoot
Ripple and noise
5 Hz - 20 MHz (See Note 1)
Temperature co-efficient
Transient response (See Note 2)
Remote sense
24 Vin nominal
48 Vin nominal
No load
Remote OFF
48 V models
(See Note 6)
Logic compatibility
ON
OFF
24 Vin: power up
24 Vin: power down
48 Vin: power up
48 Vin: power down
Power up
Remote ON/OFF
18 - 36 Vdc
36 - 75 Vdc
100 mA max.
20 mA max.
4 A max. @ Io max.
and Vin = 0 - 75 V
5 mA pk-pk
Open collector ref to -input
1.2 Vdc max.
Open circuit
17 V
16 V
34 V
32.5 V
20 ms
20 ms
60% to 110%
±1.0%
Low line to high line
±0.5%
Full load to min. load
±0.10%
0%
At turn on and turn off
None
None
3.3 V and 5 V
2 V and 15 V
±0.01% / °C
75 mV pk-pk, 20 mV rms
100 mV pk-pk, 30 mV rms
±2.0% max. deviation; 170 µs recovery to within ±1.0%
0.5 Vds transmission line drop compensation