English
Language : 

700S-CF Datasheet, PDF (9/12 Pages) Allen-Bradley – Safety Control Relays
Auxiliary Contacts
Contactors & Control Relays
Safety Control Relays
100S-C and 700S-CF
Internal Auxiliary Contacts
Catalogue Numbers
100S-C09...100S-C23
Side-Mounted Auxiliary Contacts
Catalogue Numbers
100-SA, 100-SB, 100-MC
Current Switching
AC-12 Ith
at 40°C
[A]
25
10
at 60°C
[A]
20
6
AC-15 at Rated Operating Voltage
[V] 24 48 120 240 400 415 500 690 24 48 120 240 400 415 500 690
[A] 10 10 10 10 6 5 2.5 1 6 6 6 5 3 2.5 1.6 1
DC-13 at Rated Operating Voltage
[V] 24 48 110 220 400
24 48 110 220 400
[A] 5 2 0.7 0.25 0.12
5 2 0.7 0.25 0.12
Continuous Current Rating per UL/CSA
AC
[A]
10A, 600V (NEMA A600)
10A, 600V (NEMA A600)
DC
[A]
5A, 600V (NEMA P600)
2.5A, 600V (NEMA Q600)
Short-Circuit Protection
gG Fuse
Type 2 Coordination
[A]
10
10
Rated Impulse Voltage Uimp
[kV]
8
6
Insulation Voltage (between control and load circuit) per
DIN, VDE 0106, Part 101 (NAMUR recommendation)
[V]
250
500
Contact reliability per DIN 19240 without contamination, normal
industrial atmosphere
17V, 10mA
17V, 10mA
Mechanically Linked Contacts per IEC
60947-5-1 Annex L (SUVA Third-party
certified)
Mutually unrestricted between
all N.O. and N.C. contacts
100-SA, 100-SB: Mirror output
performance per IEC60947-4 Annex F
100-MC: Mutually unrestricted
between all N.O. and N.C. contacts
Terminals
Terminal Type
Wire Size per IEC 60947-1
Flexible w/Wire-End Ferrule 1 Conductor
2 Conductor
Solid/Stranded Conductor 1 Conductor
2 Conductor
Recommended Tightening Torque (min...max)
Wire Size per UL/CSA
Recommended Tightening Torque (min...max)
[mm2]
[mm2]
[mm2]
[mm2]
Nm
[AWG]
[lb-in]
2 x A4
1…4
1…4
1.5…6
1.5…6
1...2.5
16…10
8.9…22
2 x A4
0.5…2.5
0.75…2.5
0.5…2.5
0.75…2.5
1…1.5
18…14
8.9…13.3
9-25