English
Language : 

700S-CF Datasheet, PDF (5/12 Pages) Allen-Bradley – Safety Control Relays
General (continued)
Aux.Contact
(Side-mounted)
Contact Ratings — IEC
120V
6
AC-15 (solenoids, contactors) at rated
voltage
240V
5
IEC 60947
AC-12 (Non-inductive, or
40ºC
º slightly inductive loads,
resistance furnaces), IEC60947 60 C
DC-13 (Solenoids and
contactors), IEC60947
Max. Wire Size per UL/CSA
Tightening Torque
Tightening Torque
400V
500V
Ith
Ith
24V
48V
110V
220V
440V
[AWG]
[lb-in]
[Nm]
3
1.6
10A
6A
3A
1.5A
0.6A
0.3A
0.2A
18…14
8.9…13.3
1…1.5
Control Circuit
Catalogue
Number
700S-CF
Operating Voltage
AC 50/60 Hz
DC!
Coil
Consumption
Pick-up
Dropout
Pick-up
Dropout
[x Us]
[x Us]
[x Us]
[x Us]
0.85…1.1
0.3…0.6
0.8…1.1
0.1…0.6
AC 50/60 Hz
Inrush
[VA/W]
70/50
Seal
[VA/W]
8/2.6
DC
Inrush/Seal
[W]
6.5
Operating Times
AC 50/60 Hz
Pick-up Time [ms]
15…30
Dropout Time [ms]
10…60
DC
Pick-up Time [ms]
40…70
Dropout Time [ms]
7…15
! For 9V DC, code ZR, use operating voltage 0.65…1.3 x Us.
For 24V DC, code ZJ or DJ, use operating voltage 0.7…1.25 x Us.
Contactors & Control Relays
Safety Control Relays
100S-C and 700S-CF
General (continued)
Rated Insulation Voltage Ui
IEC
UL; CSA
Rated Impulse Strength Uimp
High Test Voltage
1 minute (per IEC 947-4)
Rated Voltage Ue
AC
DC
Short-Circuit Protection IEC 158-
1 Fuse, gG
Rated Frequency
Ambient Temperature
Storage
Operation at nominal current
Conditioned 15% current
reduction after AC-1 at > 60°C
Corrosion Resistance
Altitude
Type of Protection
IP 2X (IEC 529 and DIN 40050)
Finger Protection
Catalogue Number 700S-CF
690V
600V
8 kV
2500V
115, 230, 400, 500, 690V
24, 48, 110, 220, 440V
10A
50/60 Hz, DC
–55…+80 °C (–67…176 °F)
–25…+60 °C (–13…140 °F)
–25…+70 °C (–13…158 °F)
humid-alternating climate,
cyclic, per IEC 68-2-30 and
DIN 50 016, 56 cycles
2000m above mean sea level,
per IEC 60947-4
in connected state
safe from touch by fingers and back
of hand per VDE 0106, Part 100
9-21