2030-RLSAW Datasheet, PDF (7/8 Pages) Allen-Bradley – ElectroGuard
Safety Isolation System
ElectroGuard
Typical Wiring Diagram/Wire Length Considerations
Typical Wiring Diagram
Safety Isolation System
with Optional Fusible GC
Disconnecting Means
Total Wire Length for Expansion Modules
For North America
Max. Total
Wire Gauge Wire Length
14AWG
40,000 feet
16AWG
23,000 feet
18AWG
11,700 feet
For Outside North America
Max. Total
Wire Gauge Wire Length
18 Gauge Metric 12,200 meters
14 Gauge Metric 7,000 meters
1IC 2IC
L1
T1
Sample Calculation: An application for a 630A Safety Isolation
System will require 8 Remote Lockout Stations (RLS):
L2
L3
T2 To Motor
Starters
T3
To
Loads
Designates
field
connection
points
Remote
Lockout
Station(s)
Wire Length Considerations
ATTENTION: It is important not to
exceed the maximum wire length values
shown in this section. If the maximum values
are exceeded, this may result in an unreliable
signal to the Safety Isolation System.
Consider using an Expansion Module if wire
lengths greater than those shown for the
Remote Lockout Stations are needed.
Each Remote Lockout Station is connected to the Control Module
in the Power Panel of the Safety Isolation System. The total length
of the wire used to connect the Remote Lockout Stations to the
Control Module should not exceed the maximum values shown in
the following tables.
Calculate the total wire length as follows:
1. Determine the distance in feet or meters from each Remote
Lockout Station to the Control Module (located inside the Safety
Isolation System Power Panel).
2. Sum the distances for all of the Remote Lockout Stations.
3. Double this value.
4. Compare this doubled value with the maximum values for total
wire length shown in the table below:
Total Wire Length for Remote Lockout Stations
For North America
Max. Total
Wire Gauge Wire Length
14AWG
4,600 feet
16AWG
2,600 feet
18AWG
1,300 feet
For Outside of North America
Max. Total
Wire Gauge Wire Length
18 Gauge Metric 1,400 meters
14 Gauge Metric 800 meters
The wire length from RLS # 1 to the Control Module (in the
ElectroGuard Power Panel) will be 50ft.
The wire length from RLS # 2 to the Control Module will be 200ft.
The wire length from RLS # 3 to the Control Module will be 100ft.
The wire length from RLS # 4 to the Control Module will be 300ft.
The wire length from RLS # 5 to the Control Module will be 500ft.
The wire length from RLS # 6 to the Control Module will be 1000ft.
The wire length from RLS # 7 to the Control Module will be 850ft.
The wire length from RLS # 8 to the Control Module will be 750ft.
14AWG wire will be used to connect the RLS to the Control Module
(see illustration below).
152m
(500ft)
304m
(1000ft)
259m
(850ft)
228m
(750ft)
RLS RLS
#5
#4
RLS
#8
Expansion
Module
91m (300ft)
30m (100ft)
RLS
#3
61m (200ft)
RLS
#1
Control
Module
RLS
#7
RLS
#6
RLS
#2
Power Panel
15m (50ft)
Analysis: The Control Module furnished with the 630A Safety
Isolation System is capable of supporting a maximum of six (6) RLS.
Since this installation will require eight (8) RLS, an optional 4 port
Expansion Module will also be used. The Expansion Module will be
wired to the Control Module and will take the place of one of the
original six RLS. We will, therefore, plan to wire five (5) of the RLS
directly to the Control Module and three (3) of the RLS to the
Expansion Module. Since the Expansion Module allows greater wire
lengths than the Control Module, we will plan to wire the RLS to be
installed furthest away from the Power Panel to the Expansion
Module.
If the application requires a total wire length greater than those
shown in the table, one or more Expansion Modules should be used.
The maximum wire length for the Expansion Modules is shown in
the following table:
For RLS # 1: wire length = 50ft x 2 = 100ft
For RLS # 2: wire length = 200ft x 2 = 400ft
For RLS # 3: wire length = 100ft x 2 = 200ft
For RLS # 4: wire length = 300ft x 2 = 600ft
For RLS # 5: wire length = 500ft x 2 = 1000ft
12-18