English
Language : 

2030-RLSAW Datasheet, PDF (4/8 Pages) Allen-Bradley – ElectroGuard
Safety Isolation System
ElectroGuard
Combination Systems with Thermal-magnetic Circuit Breaker/Optional Features
Product Selection for Outside of North America (see page 12-19 for Ordering Instructions)
! Bussing Designation
The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table below.
Example: Catalogue Number 2033-!0085H⊗-44K becomes Catalogue Number 2033-E0085H⊗-44K for “600A Line Side Incoming Bus and Outgoing Power
Cables” bussing designation.
Type of Bussing ➊
Catalogue Number Code
600A Line Side Incoming Bus and Outgoing Power Cables
E
1200A Line Side Incoming Bus and Outgoing Power Cables
D
Line Side Incoming Power Cables and 600A Load Side Outgoing Bus
H
Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus
R
⊗ Input Line Voltage Code
The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below.
Example: Catalogue Number 2033-C0085W⊗-48K becomes Catalogue Number 2033-C0085WN-48K for a 380V 50Hz Input Line Voltage application.
Input Line Voltage
220V 50Hz 380-400V 50Hz 400-415V 50Hz 440V 50Hz 500V 50Hz 550V 50Hz
Voltage Code for Catalogue Number
A
N
G
B
M
C
Product Selection: Remote Lockout Station ➋
“System Isolated” Light Colour
Green
IP 30 Enclosure
2030-RLSPG
Catalogue Number
IP 54 Enclosure
2030-RLSHG
IP 65 Enclosure
2030-RLSWG
Optional Features
Pneumatic Isolation Module (Must be ordered with Safety Isolation System):
The Safety Isolation System is available with an optional means of isolating the pneumatic energy source
for the machine or process. If the machine operator/maintenance personnel initiates isolation of the
electrical energy by operating one of the Remote Lockout Stations, a safety valve is simultaneously
actuated to bleed pressure from the air line between the valve and the machine. When the air pressure has
fallen to a predetermined level, the unit will allow the light on the Remote Lockout Station to illuminate,
if electrical isolation has also been achieved.
To order the Pneumatic Isolation option:
Step 1: Add the following Catalogue String to the Safety Isolation System Catalogue Number:
To indicate that the Safety Isolation
System should be supplied as “Pneumatic
Ready.”
-1PN
e.g. 2031-A0085JB-1PN to indicate an 85A Safety Isolation System that is to be “Pneumatic Ready.”
Step 2: Order suitably enclosed Pneumatic Isolation Module as separate item:
For North America:
Pressure
Range
30-120 psi
Valve Port
Size
1in
3/4in
Type 1 General
Purpose Enclosure
2030-PA1201
2030-PA1203
Catalogue Number
Type 12 Dust tight
Enclosure
Type 4 Watertight
Type 4X Watertight
Painted Steel Enclosure Stainless Steel Enclosure
2030-PJ1201
2030-PF1201
2030-PC1201
2030-PJ1203
2030-PF1203
2030-PC1203
For Outside of North America:
Catalogue Number
Pressure Range
Valve Port Size
IP 30 Enclosure
IP 54 Enclosure
IP 65 Enclosure
2-7 bar
1in
3/4in
2030-PP0071
2030-PP0073
2030-PH0071
2030-PH0073
2030-PW0071
2030-PW0073
➊ Bus Type: Copper with tin plating. Consult factory for other types of bussing.
➋ Safety Isolation Systems rated up through 85A can support a maximum of four (4) Remote Lockout Stations (RLS).
Systems rated from 110A - 1200A can support a maximum of six (6) RLS. If additional RLS are required, order the optional Expansion Module(s) (see page 12-16).
12-15