English
Language : 

100S-D Datasheet, PDF (7/8 Pages) Allen-Bradley – Safety Contactors
Coil Data
Contactors & Control Relays
Safety Contactors
100S-D
Catalogue
Number
100S- 100S- 100S- 100S- 100S- 100S- 100S- 100S- 100S- 100S-
D95 D110 D140 D140 D180 D180 D210 D250 D300 D420 100S-D630 100S-D860
Conventional
X
X
X
—
X
—
—
—
—
—
—
—
Coil Type
Electronic-EI
X
X
—
X
—
X
X
X
X
X
X
X
Voltage Range
AC: 50 Hz, 60 Hz,
50/60 Hz
DC
Coil Consumption
AC: 50 Hz, 60 Hz,
50/60 Hz
DC
Pick-up
Dropout
Pick-up
Dropout
[x Us]
[x Us]
[x Us]
[x Us]
Pick-up
Hold-in
Pick-up
Hold-in
[VA/W]
[VA/W]
[W]
[W]
0.85…1.1
0.3…0.5
0.85…1.1
0.3…0.5
370/243 ➊
12/6
190 ➊
6
590/355➊
15/7
375 ➊
7
0.85…1.1
0.3…0.8
0.80…1.1
0.3…0.8
1915/1720 ➊
33/30
1980 ➊
30
Operating Time
AC: 50 Hz, 60 Hz,
50/60 Hz
Pick-up
[ms]
Dropout [ms]
with RC Suppressor Dropout [ms]
75…90
30…60
—
75…90
30…60
—
60…100
70…145
—
Pick-up
[ms]
DC
Dropout [ms]
with Integ. Suppres. Dropout [ms]
with Diode Suppres. Dropout [ms]
75…90
30…60
—
—
75…90
30…60
—
—
60…100
70…145
—
—
➊ Electronic coil drives are designed to minimize coil consumption. However, this design may cause a large inrush (<1ms) when energizing. This must be taken into account
when sizing power supplies, all-or-nothing relays and the cross-sections of the coil wires.