100S-D Datasheet, PDF (2/8 Pages) Allen-Bradley – Safety Contactors
Contactors & Control Relays
Safety Contactors
100S-D
Product Selection
3-pole AC Contactors
• Conventional and Electronic AC Coils
• 3 Main Contacts
• Non-Reversing
Ie [A]
60°C 40°C
Switching of 3-Phase Motors—AC-2, AC-3
kW (50 Hz)
Hp (60 Hz)
Auxiliary Contacts
N.O. N.C. ➊
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V
95 160 25 50 50
55
80
45 25 30 60 75
2
110 160 32 55 55
63
100
55 40 40 75 100
2
140 250 45 75 75 80/90➌ 110/132➌ 75 40 50 100 125
2
180 250 55 90 100 90/110➌ 132/160➌ 90 50 60 150 150
2
210 350 63 110 110 150
200
110 60 75 150 200
2
250 350 80 132 150 160
250
133 75 100 200 250
2
300 450 90 160 160 200
300
163 100 125 250 300
2
420 500 132 220 250 300
425
225 150 175 350 400
2
630 800 200 355 355 450
500
425 200 250 500 600
2
860 1000 250 500 500 560
600
425 250 300 600 700
2
Catalogue Number
2
100S-D95⊗22C
2
100S-D110⊗22C
2
100S-D140⊗22C
2
100S-D180⊗22C
2
100S-D210⊗22C
2
100S-D250⊗22C
2
100S-D300⊗22C
2
100S-D420⊗22C
2
100S-D630⊗22C
2
100S-D860⊗22C
⊗ AC Coil Voltage Code
The Catalogue Number as listed is incomplete. Select a coil voltage code from the table below to complete the Catalogue Number. Example: 120V 60 Hz:
Catalogue Number 104S-C09⊗210C becomes Catalogue Number 104S-C09D210C.
Conventional Coil
V
24 48 100 110 120 200
100S-D95…
100S-D180
100S-D95…
100S-D110
50 Hz K Y — D — —
60 Hz J X — — D —
50/60 Hz KJ — KP KN — KG
220…
380…
208 230 230 240 277 400 415 440 480 500 550 600
—
A
—T— N
B G—M C—
H
— — A T — — N B —— C
—
— KF KA — — — — — — — —
Electronic Coil
42…
110…
208… 380… 440…
w/PLC Interface ➋
V
24 64 100 130 200 277 415 480 500 600
100S-D95…
100S-D250
50/60 Hz EJ EY EP ED EG EA
EN
EN EN —
100S-D300…
100S-D420
50/60 Hz — EY EP ED EG EA
EN
EN EN —
100S-D630…
100S-D860
50/60 Hz — — EP ED EG EA
EN
EB EM EC
➊ The N.C. contacts meet IEC 60947-4 Annex F requirements to mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must
be used as monitoring contacts with feedback to the safety circuit.
➋ Signal voltage of the Cat. No. 100S-D… electronic interface:Ue: 24V DC/Ie: 15 mA
Pick-Up Voltage: 13.0V DC…30.2V DC
Drop-Out Voltage: -3.0V DC…+5.0V DC
➌ Higher kW rating only applies to contactors with electronic coil.
9-10