English
Language : 

700-SK Datasheet, PDF (3/5 Pages) Allen-Bradley – Solid-State Relays
Bulletin 700-SK
Solid-State Relays
Specifications
Input Sensor Module
Cat, No.
700-SKICZ24
700-SKICA18
Rated Input
Voltage
12…24V DC
100…240V AC
Cat. No.
700-SKICZ24
700-SKICA18
Cat. No.
Pick-up time
Drop-out time
Response frequency
Output ON voltage drop
Leakage current
VDRM VCEO (V)
Output di/dt (A/uS)
Output dv/dt (V/uS)
Output I2t (A2S)
Output Tj (°C) Max.
Insulation resistance
Dielectric strength
Vibration resistance (max.)
Shock resistance (max.)
Ambient temperature
Standards
Ambient humidity
Weight
Operating
Storage
Operating
Output SSR Module
Input Sensor Ratings
Operating
Voltage Range
Input
Current
6.6…32V DC
8 mA max.
60…264V AC
15 mA max.
Output Logic Ratings
Logic Level
Supply Voltage
Pick-up Voltage
6.6V DC max.
60V AC max.
Drop-out Voltage
3.6V DC min.
20V AC min.
Logic Level
Supply Current Draw
4…32V DC
0.1…100 mA
Characteristics
700-SKICA18
700-SKICZ24
20 ms max.
0.1 ms max.
20 ms max.
0.1 ms max.
10 Hz
1 kHz
1.6 V max.
5 µA max.
80 (ref. value)
80 (ref. value)
—
—
—
—
—
—
150
150
100 MΩ min. between input and output
4,000V AC, 50/60 Hz for 1 min. between input and output
10…55 Hz, 1.5 mm double amplitude (10 G)
1,000 m/s2 (100 G)
–30…80°C (–22…176°F) with no icing or condensation
–30…100°C (–22…212°F) with no icing or condensation
UL 508
CSA C22.2
CE, TÜV
45…85% (No condensation)
Approx. 18 g
Cat. No.
700-SKOZ2Z25
700-SKON2Z25
700-SKOC2Z25
700-SKOC1Z25
Cat. No.
—
700-SKOZ2Z25
700-SKON2Z25
700-SKOC2Z25
700-SKOC1Z25
Rated Control Voltage
5…24V DC
Rated Load Voltage
—
100…240V AC
5…48V DC
48…200V DC
Control/Input Ratings
Operating Control Voltage Range
4…32V DC
Impedance➊
15 mA max.
at 25°C
(77°F)
8 mA max.
Pick-up
Voltage
4V DC
max.
Drop-out
Voltage
1V DC min.
Load/Output Ratings
Load Voltage Range
—
75…264V AC
4…60V DC
40…200V DC
Continuous Load Current
(Resistive)
Min.
Max.➌
0.05 A
2A
0.01 A
0.01 A
2A
1.5 A
Max. Inrush Current➋
—
30 A (@50/60 Hz, 1
cycle)
8 A (10 ms)
8 A (10 ms)
➊ With a constant current input system. SSR impedance varies with a change in input voltage.
➋ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 61 for more details.
➌ Refer to "Load Current Versus Ambient Temperature Characteristics" graphs on page 61 for additional details.
60