English
Language : 

AMEPR30-AZ_16 Datasheet, PDF (2/15 Pages) AIMTEC – AC-DC Constant Current or Constant Voltage LED Driver
Series AMEPR30-AZ
up to 2.5A | AC-DC / DC-DC | LED Driver / Converter
Output Specifications
Parameters
Conditions
Typical
Current accuracy
±3
Line regulation
(LL-HL)
±2
Load regulation
0-100% load
±3
Ripple & Noise*
100
Hold-up time
50
Current adjustment range⑤
100-10
④ Tested with 0.1µF (C/C) or (M/C) and 47µF (E/C) parallel capacitors at the end.
⑤ Note: from 0% to 10% dimming adjustment signal instability may be present.
Maximum
Units
%
%
%
mV p-p
ms
%
Isolation Specifications
Parameters
I/O
Tested voltage
I/FG
O/FG
Isolation resistance
Conditions
3sec
500VDC
Typical
>1000
Rated
3750
2000
500
Units
VAC
VAC
VAC
MΩ
General Specifications
Parameters
Switching frequency
Over current protection
Over voltage protection
Short circuit protection
Over temperature protection
Operating temperature
Maximum case temperature
Storage temperature
Temperature coefficient
Cooling
Humidity
Case material
Potting
Wires
Weight
Dimensions (L X W X H)
MTBF
Conditions
Typical
Maximum
130
AMEPR30-5070AZ
0.77
AMEPR30-4864AZ
0.68
AMEPR30-36100AZ
1.04
AMEPR30-24140AZ
1.45
AMEPR30-12250AZ
2.55
Refer to Constant Current vs. Constant Voltage Mode curve
Auto recovery
110~120
With derating over 55°C
Refer to model application
100
-40 to +95
±0.02
Free air convection
Non condensing
20~95
Plastic
Epoxy (IP68 rated)
UL1015 18AWG * 20CM
530
5.30 x 2.27 x 1.59 inches 134.80 x 57.68 x 40.50 mm
>400,000 hrs (MIL-HDBK-217F at t=+25°C)
Units
KHz
A
oC
oC
oC
oC
% / oC
% RH
g
Safety Specifications
Parameters
Agency approvals cULus, CE
UL8750, UL60950-1, EN55022, class B, EN60529(IP68), EN61347-1, EN61347-2-13
Information Technology Equipment
EN55022 Class B
Harmonic Current Emissions
IEC/EN 61000-3-2, Class C
Voltage fluctuations and flicker
IEC/EN 61000-3-3, (EN60555-3)
Electrostatic Discharge Immunity
IEC 61000-4-2 Level 3
Standards
RF, Electromagnetic Field Immunity
IEC 61000-4-3 Level 2
Electrical Fast Transient / Burst Immunity
IEC 61000-4-4 Level 2
Surge Immunity
IEC 61000-4-5 Level 3
RF, Conducted Disturbance Immunity
IEC 61000-4-6 Level 2
Power frequency Magnetic Field Immunity
IEC 61000-4-8 Level 1
Voltage dips, Short Interruptions Immunity
IEC 61000-4-11
www.aimtec.com
F 052.1e R3.AG
Tel: +1 514 620 2722
2 of 15
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only