English
Language : 

LAD8N20 Datasheet, PDF (1/12 Pages) Telecommunication Electronics INC – TeSys contactors
Characteristics
TeSys contactors
Model d
Type of contactor
Environment
LC1-
LC1-
LC1-
D09…D18 D25…D38 D40
DT20 & DT25 DT32…DT60
LC1-
LC1-D115 &
D50…D95 LC1-D150
Rated insulation voltage (Ui)
Conforming to EN 60947-4-1,
overvoltage category III,
degree of pollution: 3
Conforming to UL, CSA
V
690
V
600
1000
Rated impulse withstand voltage
Conforming to EN 60947
kV 6
8
(Uimp)
Conforming to standards
2
Product certifications
IEC 947-1, 947-4-1, NFC 63-110, VDE 0660, BS 5424, JEM 1038,
EN 60947-1, EN 60947-4-1.
GL, DNV, PTB, RINA pending
UL, CSA
Complies with SNCF, Sichere Trennung recommendations
Separation insulation
Conforming to VDE 0106 parts 101 V
400
and A1 (project 2/89)
Degree of protection (1)
(front face only)
Conforming to VDE 0106
Power connection
Protection against direct finger contact IP 2X
Coil connection
Protection against direct finger contact IP 2X (except LC1-D40…D80)
Protective treatment
Conforming to IEC 68
“TH”
Ambient air temperature
around the device
Storage
Operation
°C
- 60…+ 80
°C
- 5…+ 60
Permissible
°C
- 40…+ 70, for operation at Uc
Maximum operating altitude
Without derating
m
3000
Operating position
Without derating
± 30° possible, in relation to normal vertical mounting plane
Flame resistance
Conforming to UL 94
V1
Conforming to IEC 695-2-1
°C
960
Shock resistance (2)
1/2 sine wave = 11ms
Contactor open
Contactor closed
gn 10
gn 15
8
8
8
6
15
10
10
15
Vibration resistance (2)
5…300 Hz
Contactor open
gn 2
Contactor closed
gn 4
4
4
3
4
(1) Protection ensured for the connection cross-sections shown on the next page and for connection via cable.
(2) In the least favourable direction, without change of contact state (coil supplied at Ue).
Selection:
pages 1/6 to 1/35
2/32
References:
pages 2/6 to 2/9
Dimensions:
pages 2/44 to 2/47
Schemes:
pages 2/48 and 2/49
Schneider Electric