English
Language : 

SWS50 Datasheet, PDF (1/2 Pages) TDK Electronics – Single Output General Purpose Power Supplies
Single Output General Purpose Power Supplies
Features
u Low Cost
u Power Factor Correction to EN61000-3-2
u Universal Input (85 - 265VAC)
u Input Transient Protected IEC61000-4
u Enclosed
u Global safety Approvals
u Level B EMI
Key Market Segments & Applications
SWS Series
Specifications
Model
Input Voltage range
(1) -
Inrush Current (115/230VAC)
A
Power Factor
-
Input Current (115/230VAC)
A
Temperature Coefficient
-
Total Regulation
-
Overcurrent Protection
-
Overvoltage Protection
V
Hold Up Time (Typ)
ms
Leakage Current Max.
mA
Remote Sense
-
LED Indicator
-
Operating Temperature
-
Storage Temperature
-
Operating Humidity
(2) °C
Storage Humidity
(2) °C
Cooling
-
Withstand Voltage
-
Isolation Resistance
-
Vibration (non operating)
-
Shock
-
Safety Agency Approvals
-
Conducted & Radiated EMI
-
Recommended EMI Filter
-
Immunity
-
Weight (Typ)
g
Size (WxHxD)
in
Warranty
yrs
SWS50
SWS75
SWS100
SWS150
85 - 265VAC (47 - 63Hz) or 120 - 370VDC
20/40
16/32
Meets EN61000-3-2
1.2/0.6
1.6/0.8
1.2/0.6
1.8/0.9
<0.02%/°C
<5%
>105%, Constant Current Style
115 -135%, Cycle AC line to reset
20ms at 115VAC
1mA (0.6mA typ@230VAC)
0.75mA (0.5mA typ@230VAC)
Not Available
Green LED = On
-10 to +70°C (See table for derating - model specific)
-30 to +85°C
30 - 90% RH
10 - 95% RH
Convection
Input to Ground 2kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
>100M at 25°C & 70%RH, Output to Ground 500VDC
19.6m/s2 (10 - 55Hz (constant sweep 1 min) X, Y, Z for 1 hour)
< 196.1 m/s2 (20G)
UL60950-1, CSA60950-1, EN60950-1, CE Mark, EN50178
EN55011 / EN55022-B, FCC Class B, VCCI-B
RSEL-2002W
RSEL-2003W
RSEL-2002W
RSEL-2003W
EN61000-4-2,-3,-4,-5,-6,-8,-11
400
480
600
750
3.62 x 1.46 x 6.26 3.7 x 1.69 x 6.69 3.78 x 1.77 x 7.4
3.9 x 2 x 7.8
Two Years
(1) Derate to 85% load below 100VAC input (2) non condensing
1-800-526-2324 • www.us.tdk-lambda.com/lp/
95
Disclaimer: us.tdk-lambda.com/lp/legal.htm