English
Language : 

YR40.241 Datasheet, PDF (1/17 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YR40.241
12-28V, 40A, DUAL REDUNDANCY MODULE
MOSFET REDUNDANCY MODULE
ƒ For N+1 and 1+1 Redundant Systems
ƒ Dual Input with Single Output
ƒ Suitable for all Power Supplies
ƒ Only 72mV Voltage Drop at 20A Output Current
ƒ Only 2.15W Loss at 20A and 6.3W at 40A Output Current
ƒ 160% (65A) Peak Load Capability
ƒ Reverse Input Polarity Protection
ƒ Full Power Between -40°C and +70°C
ƒ Width only 36mm
ƒ Rugged Metal Housing
ƒ Easy Wiring:
Distribution Terminal for Negative Pole Included
ƒ 3 Year Warranty
GENERAL DESCRIPTION
The YR40.241 is a redundancy module, which can be
used to build 1+1 and N+1 redundant systems. It is
equipped with two input channels, which can be
connected to power supplies with up to 20A output
current and one output, which can carry nominal
currents up to 40A. The module is suitable for power
supplies with constant current overload behavior as well
as any kind of “Hiccup” overload behavior. In addition
to the YR40.241, the YR40.242 is also available which is
cost-optimized and suitable for all DIMENSION power
supplies except the QT20 and QTD20 series.
The novelty of this redundancy module is the utilization
of mosfets instead of diodes for the decoupling of the
two input channels. This reduces the heat generation
and the voltage drop between input and output. The
redundancy module does not require an additional
auxiliary voltage and is self-sufficient even in case of a
short circuit across the output.
Due to the low power losses, the unit is very slender and
only requires 36mm width on the DIN-rail. Large
connection terminals allow for a safe and fast
installation with a large international approval package.
This unit is suitable for nearly every application.
ORDER NUMBERS
Redundancy YR40.241
Module
12-28V Standard unit
Accessory
ZM2.WALL
ZM11.SIDE
Wall/ panel mount
bracket
Side mount bracket
SHORT-FORM DATA
Input voltage
DC 12-28V
±30%
Input voltage
8.4-36.4Vdc
range
Input current
2x 0-20A
continuous
2x 20-32.5A
for 5 seconds
Output current
0-40A
continuous
40-65A
for 5 seconds
65A
at cont. overload
or short circuit
Input to output
typ. 72mV
input: 2x10A
voltage drop
typ. 112mV
input: 1x20A
typ. 140mV
input: 2x20A
Power losses
typ. 700mW
at no load
typ. 2.15W
input: 2x10A
typ. 2.65W
input: 1x20A
typ. 6.3W
input: 2x20A
Temperature range -40°C to +70°C operational,
no de-rating req.
Dimensions
36x124x127mm*) WxHxD
*) plus 4mm in depth for the screw terminal
MARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
IECEx
ATEX
II 3G Ex nA IIC T4 Gc
Marine
Class I Div 2
EMC, LVD
Feb. 2014 / Rev. 1.3 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany