LPQ201-M Datasheet, PDF (1/3 Pages) Artesyn Technologies – Total Power: 100 - 200 Watts | |||
|
POWER
Data Sheet
Total Power: 100 - 200 Watts
Input Voltage: 90 - 264 Vac
# of Outputs: Quad
SPECIAL FEATURES
ÂÂ Medical and ITE safeties
ÂÂ Active power factor correction
ÂÂ 3â x 5â footprint
ÂÂ Less than 1U high
ÂÂ EN61000-3-2 compliant
ÂÂ Remote sense
ÂÂ Power fail
ÂÂ Adjustable outputs
ÂÂ Built-in Class B EMI filter
ÂÂ Overvoltage protection
ÂÂ Overload protection
ÂÂ Thermal overload protection
ÂÂ LPX200 enclosure kit available
ÂÂ RoHS compliant
SAFETY
ÂÂ TUV
ÂÂ UL
ÂÂ CSA
ÂÂ CB
ÂÂ CE
60950, 60601-1
60950, 60601-1
60950, 60601-1
Certificate & report
Mark (LVD)
LPQ200-M Series
200 Watts
Electrical Specifications
Input
Input raÂnge
90 - 264 Vac; 120 - 300 Vdc
Frequency
47 - 63 Hz
Inrush current
50 A max., cold start @ 25 °C, 230 Vac input
Efficiency
84% typical at full load
EMI/RFI
FCC Class B conducted; CISPR22 Class B conducted;
EN55022 Class B conducted; VDE0878PT3 Class B conducted
Safety ground
leakage current
275 μA @ 50/60 Hz, 264 Vac input
Output
Maximum power
100 W for convection; 200 W with 30CFM forced air
Adjustment range
All outputs -20%, +10%, except for the 3.3 V output which will be
-15%, +10% (LPQ201-M)
Hold-up time
16 ms @ 200 W load, 120 Vac input
Overload protection
Short circuit protection on all outputs. V1, V2 & V3 overload protected
@ 110 - 160%. V4 is 150 - 250% above rating
Overvoltage protection 30 - 50% above nominal output on V1 (and V2 on LPQ201-M)
Logical Control
Power failure
Active low logic signal goes high 100-500 msec after main output; it
goes low at least 6 msec before loss of regulation
Remote sense
Compensates for 0.4 V lead drop min. Will operate without remote
sense connected. Reverse connection protected.
|
▷ |