600 800 Watts
SMR Series
xppower.com
⢠Up to 900 W Peak Output Power
⢠Single Outputs from 12 V to 48 V
⢠Compact Size
⢠Remote On/Off
⢠SEMI F47 Compliant
⢠Optional Current Share
⢠3 Year Warranty
Specification
Input
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
Earth Leakage Current
Input Protection
⢠90-264 VAC (120-370 VDC)
⢠47-63 Hz
⢠SMR600: 9 A at 90 VAC, 3.5 A at 230 VAC
SMR800: 11 A at 90 VAC, 5 A at 230 VAC
⢠70 A at 230 VAC
⢠>0.9
⢠<2.4 mA max at 264 VAC
⢠Fitted with a T12 A/250 V fuse
Output
Output Voltage
⢠See table
Output Voltage Trim ⢠±5%
Initial Set Accuracy ⢠±1%
Minimum Load
⢠1% (see note 9)
Start Up Delay
⢠1.5 s at 230 VAC
Start Up Rise Time
⢠40 ms typical
Hold Up Time
⢠16 ms min at 120 VAC
Line Regulation
⢠±0.5%, low line to high line
Load Regulation
⢠±1%, 1-100% load (see note 8)
Over/Undershoot
⢠5% max
Transient Response
⢠5% max deviation, 500 µs recovery to
within 1% for a 50% load change
Ripple & Noise
⢠1% of nominal output voltage (see note 2)
Overvoltage Protection ⢠110-130% recycle input to reset
Overtemperature
Protection
⢠Measured internally with auto recovery
Overload Protection ⢠110-140% with auto recovery
Short Circuit Protection ⢠Trip and restart (Hiccup mode)
Remote Sense
⢠Compensates for up to 0.5 V line drop
(not available with current share)
Remote On/Off
⢠On = TTL Logic HIGH, or open circuit
Off = TTL Logic LOW or short circuit
Current Share
⢠Optional single wire current share
within 10% for up to 4 units
(add suffix â-Iâ to model number)
Note that this option includes output
blocking diodes. Remote sense is not
available with current share.
General
Efficiency
Isolation
Switching Frequency
Power Density
Signals
Current Monitor
MTBF
⢠See model table
⢠3000 VAC Input to Output
1500 VAC Input to Ground
250 VDC Output to Ground
⢠60 kHz PFC, 25 kHz PWM typical
⢠SMR600: 6.16 W/In3, SMR800: 8.2 W/In3
⢠Green LED for Power On, Power Good
TTL HIGH within 100-500 ms and LOW
â¤1 ms before loss of regulation
⢠0.5 V to 3 V output denoting
0-100% output current
⢠150 kHrs min to MIL-HDBK-217F
at 25 °C, GB
Environmental
Operating Temperature ⢠0 °C to +70 °C, derates from 100% load at
+50 °C to 50% load at +70 °C
Cooling
⢠Integral fan
Operating Humidity ⢠5-90%, non-condensing
Storage Temperature ⢠-20 °C to +85 °C
Operating Altitude
⢠3000 m
Vibration
⢠5-50 Hz, acceleration 7.35 ms2 on
X, Y and Z axis
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Dips & Interruptions
Safety Approvals
⢠FCC Part 15 & EN55022, level B
conducted and radiated
⢠EN61000-3-2 class A
EN61000-3-2 class C for loads â¥20%
⢠EN61000-3-3
⢠EN61000-4-2, level 3 Perf Criteria A
⢠EN61000-4-3, 3 V/m Perf Criteria A
⢠EN61000-4-4, level 2 Perf Criteria A
⢠EN61000-4-5, installation class 3
Perf Criteria A
⢠EN61000-4-6, 3V Perf Criteria A
⢠EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms Perf Criteria A, B, B
⢠UL60950, CSA C22.2 No. 950,
EN60950-1:2001, CE Mark LVD,
SEMI F47 compliant (high line only) at
100% rated power output
|
▷ |