English
Language : 

SMR600 Datasheet, PDF (1/4 Pages) XP Power Limited – 600-800 Watts SMR Series
600 800 Watts
SMR Series
xppower.com
• Up to 900 W Peak Output Power
• Single Outputs from 12 V to 48 V
• Compact Size
• Remote On/Off
• SEMI F47 Compliant
• Optional Current Share
• 3 Year Warranty
Specification
Input
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
Earth Leakage Current
Input Protection
• 90-264 VAC (120-370 VDC)
• 47-63 Hz
• SMR600: 9 A at 90 VAC, 3.5 A at 230 VAC
SMR800: 11 A at 90 VAC, 5 A at 230 VAC
• 70 A at 230 VAC
• >0.9
• <2.4 mA max at 264 VAC
• Fitted with a T12 A/250 V fuse
Output
Output Voltage
• See table
Output Voltage Trim • ±5%
Initial Set Accuracy • ±1%
Minimum Load
• 1% (see note 9)
Start Up Delay
• 1.5 s at 230 VAC
Start Up Rise Time
• 40 ms typical
Hold Up Time
• 16 ms min at 120 VAC
Line Regulation
• ±0.5%, low line to high line
Load Regulation
• ±1%, 1-100% load (see note 8)
Over/Undershoot
• 5% max
Transient Response
• 5% max deviation, 500 µs recovery to
within 1% for a 50% load change
Ripple & Noise
• 1% of nominal output voltage (see note 2)
Overvoltage Protection • 110-130% recycle input to reset
Overtemperature
Protection
• Measured internally with auto recovery
Overload Protection • 110-140% with auto recovery
Short Circuit Protection • Trip and restart (Hiccup mode)
Remote Sense
• Compensates for up to 0.5 V line drop
(not available with current share)
Remote On/Off
• On = TTL Logic HIGH, or open circuit
Off = TTL Logic LOW or short circuit
Current Share
• Optional single wire current share
within 10% for up to 4 units
(add suffix ‘-I’ to model number)
Note that this option includes output
blocking diodes. Remote sense is not
available with current share.
General
Efficiency
Isolation
Switching Frequency
Power Density
Signals
Current Monitor
MTBF
• See model table
• 3000 VAC Input to Output
1500 VAC Input to Ground
250 VDC Output to Ground
• 60 kHz PFC, 25 kHz PWM typical
• SMR600: 6.16 W/In3, SMR800: 8.2 W/In3
• Green LED for Power On, Power Good
TTL HIGH within 100-500 ms and LOW
≤1 ms before loss of regulation
• 0.5 V to 3 V output denoting
0-100% output current
• 150 kHrs min to MIL-HDBK-217F
at 25 °C, GB
Environmental
Operating Temperature • 0 °C to +70 °C, derates from 100% load at
+50 °C to 50% load at +70 °C
Cooling
• Integral fan
Operating Humidity • 5-90%, non-condensing
Storage Temperature • -20 °C to +85 °C
Operating Altitude
• 3000 m
Vibration
• 5-50 Hz, acceleration 7.35 ms2 on
X, Y and Z axis
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Dips & Interruptions
Safety Approvals
• FCC Part 15 & EN55022, level B
conducted and radiated
• EN61000-3-2 class A
EN61000-3-2 class C for loads ≥20%
• EN61000-3-3
• EN61000-4-2, level 3 Perf Criteria A
• EN61000-4-3, 3 V/m Perf Criteria A
• EN61000-4-4, level 2 Perf Criteria A
• EN61000-4-5, installation class 3
Perf Criteria A
• EN61000-4-6, 3V Perf Criteria A
• EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms Perf Criteria A, B, B
• UL60950, CSA C22.2 No. 950,
EN60950-1:2001, CE Mark LVD,
SEMI F47 compliant (high line only) at
100% rated power output