PBM300PS03-C Datasheet, PDF (1/2 Pages) XP Power Limited – AC-DC Power Supplies
300 Watts
PBM300 Series
xppower.com
• Worldwide Medical Approvals
• Single and Quad Outputs
• Small Size - Only 7.50” x 4.50” x 1.75”
• Power Fail Detect & Remote On/Off
• Universal AC Input with Active PFC
• High Reliability >300 kHrs MTBF
• 150 Watt Convection-cooled Rating
Specification
Input
Input Voltage
• 90-264 VAC
Input Frequency
• 47-63 Hz
Input Current
• 4.7 A rms at 115 VAC,
2.3 A rms for 230 VAC
Inrush Current
• 30 A at 115 VAC,
60 A at 230 VAC cold start +25 °C
Power Factor
• 0.98 typical
Earth Leakage Current • 100 µA max at 115 VAC/60 Hz
220 µA max at 230 VAC/50 Hz
Input Protection
• Both line and neutral fused
Output
Output Voltage
• See table
Output Voltage Trim • ±5% for outputs 1 & 2
Initial Set Accuracy • ±2%
Minimum Load
• See table and note 5
Start Up Delay
• 2 s max
Start Up Rise Time
• 18 ms typical
Hold Up Time
• 12 ms min at full load and 110 VAC
Drift
• ±0.2%
Line Regulation
• ±0.2% max
Load Regulation
• See note 6
Transient Response
• 4% max deviation, recovery to within
1% in 500 µs for a 25% load change
Ripple & Noise
• 2% max pk-pk, 20 MHz BW, with a 22 µF
electrolytic & a 0.47 µF tantalum capacitor
Overvoltage Protection • 115-140% Vnom output 1 only, recycle
input to reset
Overtemperature
Protection
• Shutdown at +95 °C (singles) or +105 °C
(multi-outputs) with auto recovery,
measured internally
Overload Protection • 140-200% typical, auto recovery
Short Circuit Protection • Trip and restart (Hiccup mode)
Temperature
Coefficient
• 0.04%/°C
Remote Sense
• Compensates for up to 0.5 V drop
Remote On/Off
• On = Logic low or open circuit
Off = Logic high
General
Efficiency
Isolation
Switching Frequency
Power Density
Power Fail Detect
MTBF
• 70% typical
• 4000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
• 70 kHz ±10 kHz
• 5.08 W/In3
• AC OK = TTL logic high
AC not OK = TTL logic low
• 300 kHrs per MIL-HDBK-217F at +25 °C
Environmental
Operating Temperature • 0 °C to +70 °C, derate linearly from 100%
power at +50 °C to 50% power at +70 °C
Cooling
• ‘C’ versions have internal fan,
‘B’ versions are derated with convection
cooling or require 35 CFM (see note 4)
Operating Humidity • up to 95% RH, non-condensing
Storage Temperature • -40 °C to +85 °C
Operating Altitude
• 2500 m
Shock
• Half sine pulse. acceleration 50 g,
duration 11 ms, 3 shocks in each
direction, unpackaged, non-operating
Vibration
• Sinusoidal 10-50 Hz, amplitude 0.15 mm,
30 min/axis, unpackaged, non-operating
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Dips & Interruptions
Safety Approvals
• EN55011 and FCC Class B conducted
& radiated
• EN61000-3-2
• EN61000-3-3
• EN61000-4-2, level 3 Perf Criteria A
• EN61000-4-3, level 3 Perf Criteria A
• EN61000-4-4, level 3 Perf Criteria A
• EN61000-4-5, level 3 Perf Criteria A
• EN61000-4-6, 3 V Perf Criteria A
• EN61000-4-11, 30% 10 ms,
60% 100 ms, >95% 5000 ms,
Perf Criteria A, A, B
• EN60601-1, UL60601-1,
CSA22.2 No. 601-1 per cUL, CE Mark