English
Language : 

PBM200 Datasheet, PDF (1/2 Pages) XP Power Limited – 200 Watts PBM200 Series
200 Watts
PBM200 Series
xppower.com
• Worldwide Medical Approvals
• Single, Dual, Triple and Quad Outputs
• Power Fail Detect
• Remote On/Off
• U Channel and Enclosed Versions
• 100 Watt Convection cooled Rating
• 3 Year Warranty
Specification
Input
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
Earth Leakage Current
Input Protection
• 90-264 VAC
• 47-63 Hz
• 3.2 A rms at 115 VAC,
1.6 A rms at 230 VAC
• 20 A at 115 VAC, 40 A at 230 VAC
cold start 25 °C
• 0.98 typical
• 90 µA max at 115 VAC/60 Hz
150 µA max at 230 VAC/50 Hz
• Internal T4 A/250 V in line and neutral
Output
Output Voltage
• See table
Output Voltage Trim • Not user-adjustable
Initial Set Accuracy • ±2%
Minimum Load
• See table & note 5
Start Up Delay
• 2 s max
Start Up Rise Time
• 18 ms typical
Hold Up Time
• 20 ms minimum at full load & 110 VAC
Drift
• ±0.2%
Line Regulation
• ±0.5% max
Load Regulation
• See note 7
Transient Response
• 4% max deviation, recovery to within
1% in 500 µs for a 25% load change
Ripple & Noise
• 2% max pk-pk, 20 MHz bandwidth with
a 22 µF electrolytic & a 0.47 µF tantalum
capacitor
Overvoltage Protection • 112-140% Vnom output 1 only, recycle
input to reset
Overtemperature
Protection
• Shutdown at +85 °C (singles) or +105 °C
(multi outputs) with auto recovery,
measured internally
Overload Protection • 110-150% typical, auto recovery
Short Circuit Protection • Trip and restart (Hiccup mode)
Temperature
Coefficient
• 0.04%/°C
Remote Sense
• Single output models only.
Compensates for up to 0.5 V drop
Remote On/Off
• On = Logic low or open circuit
Off = Logic high
General
Efficiency
Isolation
Switching Frequency
Signals
Power Density
Power Fail Detect
MTBF
• 80% maximum
• 4000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
• 100 kHz ±12 kHz
• Power fail detect, remote on/off
• 4.76 W/In3
• AC OK = TTL logic high
AC not OK = TTL logic low
• 350 kHrs to MIL-HDBK-217F at
+25 °C, GB
Environmental
Operating Temperature • 0 °C to +70 °C, derate linearly from 100%
power at +50 °C to 50% power at +70 °C
Cooling
• ‘C’ versions have internal fan,
‘B’ versions are derated with convection
cooling or require 25 CFM (see note 4)
Operating Humidity • Up to 95% RH, non-condensing
Storage Temperature • -40 °C to +85 °C
Operating Altitude
• 2500 m
Shock
• Half sine pulse. acceleration 50 g, 11 ms
duration, 3 shocks in each direction,
unpackaged, non-operating
Vibration
• Sinusoidal 10-55 Hz, amplitude 0.15 mm,
30 min/axis, unpackaged, non-operating
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Dips & Interruptions
Safety Approvals
• EN55011 & FCC Class B conducted
& radiated
• EN61000-3-2, Class A
• EN61000-3-3
• EN61000-4-2, level 3 Perf Criteria A
• EN61000-4-3, level 3 Perf Criteria A
• EN61000-4-4, level 3 Perf Criteria A
• EN61000-4-5, level 3 Perf Criteria A
• EN61000-4-6 3 V, Perf Criteria A
• EN61000-4-11, 30% 10 ms,
60% 100 ms, >95% 5000 ms,
Perf Criteria A, B, B
• EN60601-1, UL60601-1,
CSA22.2 No. 601-1 per cUL