Low Volt Disconnect Module
Up To 30 A
LVD Series
THE XPERTS IN POWER
•
Up To 30 A Maximum Current
•
Deep Discharge Pre-Warning Alarm
•
Din Rail Mounting
•
Automatic Reset
•
12, 24 & 48 VDC
Specification
Input
Operating
•
Voltage Range
Output
LVD Relay Contacts •
LVD Alarm Set Range •
Pre-Warning
•
Disconnect
General
Alarm Relay Contacts •
Screw Terminal Sizes •
Mounting
•
-25% to +30% output voltage
1 pole changeover - See Table for
current rating
-35 to +10% output voltage
(user adjustable)
-35 to +10% output voltage
(user adjustable)
1 pole changeover, 1 A 24 VDC
Input - suitable for 1.0 mm2 cable,
LVD - suitable for 2.5 mm2 cable,
Alarms - suitable for 1mm2 cable
DIN Rail
Mechanical Details
Environmental
Operating
•
Temperature
Storage
•
Temperature
Humidity
•
0 °C to +50 °C (40 °C ambient plus
+10 °C rise inside enclosure)
-40 °C to +85 °C
90% non-condensing
Output
Voltage
12 V
24 V
48 V
LVD SERIES
Output
Current
30 A
20 A
10 A
Model
Number
LVD12
LVD24
LVD48
PSU
SCHEMATIC
F1
F2
NOTES:
1. All dimensions in mm.
2. Weight 0.11 Kg.
3. Alarm contacts shown in de-energised state.
•