6 Watts
xxx Series • International Medical Approvals
• 4000 VAC Reinforced Insulation
• Meets IEC60601-1, 3rd Edition
• 2 MOPP Isolation at 250 VAC
• 2 µA Patient Leakage Current
• DIP24 Package
• EN55011 Level A With No External Components
• 3 Year Warranty
Models & Ratings
Input Voltage
10-17 V
20-30 V
Output Voltage
5.0 V
12.0 V
15.0 V
±12.0 V
±15.0 V
5.0 V
12.0 V
15.0 V
±12.0 V
±15.0 V
Output Current
1200 mA
500 mA
400 mA
±250 mA
±200 mA
1200 mA
500 mA
400 mA
±250 mA
±200 mA
Dimensions:
JHL06:
1.25 x 0.80 x 0.40” (31.15 x 20.32 x 10.20 mm)
Input Current
No Load(1)
Full Load(2)
59 mA
640 mA
92 mA
640 mA
79 mA
605 mA
52 mA
605 mA
68 mA
600 mA
38 mA
315 mA
34 mA
300 mA
23 mA
290 mA
29 mA
295 mA
33 mA
295 mA
Maximum
Capacitive Load(3)
1200 µF
500 µF
400 µF
±250 µF
±250 µF
1200 µF
500 µF
400 µF
±250 µF
±250 µF
Efficiency(4)
78%
78%
82%
83%
83%
78%
83%
85%
85%
83%
Model Number
JHL0612S05
JHL0612S12
JHL0612S15
JHL0612D12
JHL0612D15
JHL0624S05
JHL0624S12
JHL0624S15
JHL0624D12
JHL0624D15
Notes
1. Input current measured at nominal input voltage.
2. Input current measured at lowest input voltage.
3. Maximum capacitive load is per output.
4. Typical values.
Mechanical Details
1.25
(31.75)
0.80
(20.32)
0.20
(5.08)
0.10
(2.54)
14 16
22 23
Bottom View
0.60
(15.24)
11 10 9
32
0.18
(4.57)
0.90
(22.86)
0.40 (10.20)
0.12 (3.05) Min.
Notes:
1. Pin diameter: 0.02 ±0.002 (0.5 ±0.05)
2. Pin pitch tolerance: ±0.014 (±0.35)
3. Case Tolerance: ±0.02 (±0.5)
Pin Connections
Pin
Single
Dual
2
-Vin
-Vin
3
-Vin
-Vin
9
No Pin
Common
10
Trim
Trim
11
No Pin
-Vout
14
+Vout
+Vout
16
-Vout
Common
22
+Vin
+Vin
23
+Vin
+Vin
Notes
1. All dimensions are in inches (mm)
2. Weight: 0.04 lbs (20 g) approx.
3. Pin diameter: 0.02 ±0.002 (0.5 ±0.05)
4. Pin pitch tolerance: ±0.014 (±0.35)
5. Case tolerance: ±0.02 (±0.5)
1