English
Language : 

IFC125-14 Datasheet, PDF (1/2 Pages) XP Power Limited – AC-DC Power Supplies
125 Watts
IFC125 Series
xppower.com
• Small Size - 3.0” x 5.0” x 1.25”
• Single, Triple and Quad Outputs
• Active PFC - Meets EN61000-3-2, -3
• Current Share up to 4 Units
• Overvoltage & Overcurrent Protection
• Power Good Signal
• -25 ˚C to +50 ˚C Full Power
Specification
Input
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
Earth Leakage Current
Input Protection
• 90-264 VAC
• 47-63 Hz
• 0.8 A max at 240 VAC
1.8 A max at 100 VAC
• 33 A max at 115 VAC
66 A max at 230 VAC
• 0.98 typical
• 0.5 mA max at 132 VAC/60Hz
0.825 mA max at 264 VAC/50Hz
• Internal 2.6 A fuse
Output
Output Voltage
• See table
Output Voltage Trim • Not user-adjustable
Initial Set Accuracy • ±5% maximum
Minimum Load
• 5 W minimum load on V1 or V2 required
to maintain regulation
Start Up Delay
• 1.5 s at 90 VAC
Start Up Rise Time
• 0.2-20 ms
Hold Up Time
• >28 ms min at full load
Line Regulation
• See table
Load Regulation
• See table
Over/Undershoot
• 10% maximum
Transient Response
• 5% max. deviation, recovery to within
1% in 500 µs for a 25% load change
Ripple & Noise
• ±1% pk-pk maximum or ≤5 Vout 50 mV
maximum
Overvoltage Protection • V1 & V2: 113-148%, auto recovery
Overtemperature
Protection
• Unit shuts down, recycle input to reset
Overload Protection • All outputs: 115-135%, auto recovery
Short Circuit Protection • Trip and restart (Hiccup mode)
Temperature
Coefficient
• 0.04% / ˚C maximum
Remote Sense
• V1 only compensates for 0.5 V drop (not
available on IFC125-31)
Current Share
• Up to 4 supplies to share within 10%
General
Efficiency
Isolation
Power Density
Signals
MTBF
• 83% typical
• 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
• 6.66 W/In3
• Power Good - On = Logic High
• >220 kHrs per Bellcore
Environmental
Operating Temperature • -25 ˚C to +70 ˚C, derate linearly from
100% at +50 ˚C to 50% at +70 ˚C
Cooling
• 5 CFM airflow required for 125 W
Operating Humidity • 5-95% RH, non-condensing
Storage Temperature • -40 ˚C to +85 ˚C
Operating Altitude
• 3000 m
Shock
• 15 G pk operating
Vibration
• 2.4 G, 5 Hz to 500 Hz, 3 axis
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Dips & Interruptions
Safety Approvals
• EN55022/CISPR22 and FCC, Class
B conducted
• EN61000-3-2
• EN61000-3-3
• EN61000-4-3, level 3 Perf Criteria B
• EN61000-4-4, level 3 Perf Criteria B
• EN61000-4-5, level 3 Perf Criteria B
• EN61000-4-6
• EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms, Criteria A, B, B
• EN60950, UL 60950, CSA950 per cUL,
CE Mark LVD
1