FCM Datasheet, PDF (1/2 Pages) XP Power Limited – 400 W Continuous, 600 W Peak | |||
|
400 Watts
FCM Series
xppower.com
⢠400 W Continuous, 600 W Peak
⢠IT and Medical Approvals
⢠80 V 275 VAC Operation
⢠Low Noise Fan
⢠Screw Terminals
⢠5 V Standby, AC OK and Remote On/Off
⢠3 Year Warranty
Specification
Input
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
Earth Leakage Current
Input Protection
⢠80-275 VAC, derate output power
<90 VAC (see derating curve)
⢠47-63 Hz
⢠4.1 A at 115 VAC typical
2.1 A at 230 VAC with 400 W load
⢠60 A max at 264 VAC, cold start 25 °C
⢠>0.9
⢠260 µA max, 264 VAC, 60 Hz
⢠F10 A / 250 V internal fuse in line
and neutral
Output
Output Voltage
⢠12-48 VDC (see tables)
Output Voltage Trim ⢠±10% V1
Initial Set Accuracy ⢠±1% V1, ±5% V2
Minimum Load
⢠No minimum load required
Start Up Delay
⢠1 s typical
Start Up Rise Time
⢠50 ms
Hold Up Time
⢠20 ms minimum
Line Regulation
⢠±0.5% maximum
Load Regulation
⢠±1% V1, ±5% V2
Transient Response
⢠4% max. deviation, recovery to
within 1% in 500 µs for a 50-75-50%
load change
Ripple & Noise
⢠1% pk-pk, 20 MHz bandwidth
Overvoltage Protection ⢠115-140% Vnom, recycle input to reset
Overtemperature
Protection
⢠Auto reset
Overload Protection ⢠150-165%, V1 only
Short Circuit Protection ⢠Continuous, approximately constant
current
Temperature
Coefficient
⢠0.05% / °C
Remote On/Off
⢠Uncommitted isolated optocoupler diode,
powered diode inhibits V1 & Fan
General
Efficiency
Isolation
Switching Frequency
Power Density
Signals
MTBF
⢠85% typical
⢠4000 VAC input to output, 2 x MOPP,
1500 VAC input to ground, 1 x MOPP,
500 VAC output to ground
⢠PFC 70 kHz, main converter 65 kHz typical
⢠8.6 W/in3
⢠AC OK, remote on/off, 5 V standby
⢠236 kHrs to MIL-HDBK-217F at 25 °C, GB
Environmental
Operating Temperature ⢠-10 °C to +70 °C, derate linearly
from +50 °C at 2.5% / °C to 50%
load at +70 °C
Cooling
⢠Forced cooled with integral fan
Operating Humidity ⢠95% RH, non-condensing
Storage Temperature ⢠-40 °C to +85 °C
Operating Altitude
⢠3000 m
Shock
⢠30 g pk, half sine, 6 axes
Vibration
⢠2 g rms, 5 Hz to 500 kHz, 3 axes
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Dips & Interruptions
Safety Approvals
⢠EN55011/22 level B conducted
EN55011/22 level A radiated
⢠EN61000-3-2, class A
EN61000-3-2, class C for loads â¥50%
⢠EN61000-3-3
⢠EN61000-4-3, level 3 Perf Criteria A
⢠EN61000-4-4, level 3 Perf Criteria A
⢠EN61000-4-5, installation class 3,
Perf Criteria A
⢠EN61000-4-6, level 3, Perf Criteria A
⢠EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms, Perf Criteria A, B, B,
EN60601-1-2, 30% 500 ms, 60% 100 ms,
100% 10 ms, 100% 5000 ms, Perf Criteria
A, A, A, B - 230 VAC. Consult longform
datasheet for 115 V operation
⢠IEC60950-1 CB report, UL60950-1, TUV,
EN60950-1, IEC60601-1 CB report, CSA
22.2 No.60601-1, ANSI/AAMI ES60601-1,
TUV60601-1, including risk management
|
▷ |