|
DNR960TS24-I Datasheet, PDF (1/2 Pages) XP Power Limited – AC-DC Power Supplies | |||
|
960 Watts
DNR960 Series
xppower.com
⢠Rugged Design for Industrial Applications
⢠Up to 93% Typical Efficiency
⢠Wide Adjustment Range
⢠Full Power to 60 ºC
⢠Three Phase Operation
⢠Single Phase Operation
⢠70 ºC Convection Operation.
Specification
Input
Input Voltage
⢠340-575 VAC 3à (1à operation with 75%
output derating), 480-820 VDC
Input Frequency
⢠47-63 Hz
Input Current
⢠1.6 A at 500 VAC
Inrush Current
⢠30 A typical at 500 VAC, cold start
Power Factor
⢠0.7 at 500 VAC input and nominal load
Earth Leakage Current ⢠0.32 mA
Output
Output Voltage
⢠See table
Output Voltage Trim ⢠See table
Initial Set Accuracy ⢠±1%
Minimum Load
⢠No minimum load required
Start Up Delay
⢠<150 ms
Start Up Rise Time
⢠<50 ms
Hold Up Time
⢠20 ms min at 400 VAC
Line Regulation
⢠±1%
Load Regulation
⢠±1% (±5% for units in parallel)
Transient Response
⢠4% max deviation recovering to within 1%
in 200 µs for 50% load change
Ripple & Noise
⢠80 mV pk-pk 20 MHz BW
Overvoltage Protection ⢠125-140%, recycle input to reset
Overload Protection ⢠Continuous current limit
Temperature
Coefficient
⢠±0.02%/°C
Current Share
⢠2 units can be paralleled.
Total output derates by 10%
General
Efficiency
Isolation
Switching Frequency
Signals
MTBF
⢠See table
⢠3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
⢠25 KHz typical
⢠DC ON indicator LED Green,
DC LOW indicator LED Red
DC OK: normally open relay on
24 V models
⢠370 Khrs to Bellcore, SR-332 issue 6,
Model 3
Environmental
Operating Temperature ⢠-25 ºC to 70 ºC, derate linearly from 60 ºC
at 3.5%/ºC (see derating curve)
Cooling
⢠Convection-cooled
Operating Humidity ⢠20-95% RH, non-condensing
Storage Temperature ⢠-25 °C to +85 °C
Shock
⢠4 g peak, 22 ms on X, Y and Z axis
Vibration
⢠10 to 500 Hz, 1 g rms on X, Y and Z axis
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Magnetic Field
Dips & Interruptions
Safety Approvals
⢠EN55022, class B conducted & radiated
⢠EN61000-3-2, class A
⢠EN61000-3-3
⢠EN61000-4-2, level 4 perf criteria A
⢠EN61000-4-3, level 3 perf criteria A
⢠EN61000-4-4, level 4 perf criteria A
⢠EN61000-4-5, level 3 perf criteria A
⢠EN61000-4-6, level 3 perf criteria A
⢠EN61000-4-8, level 4 perf criteria A
⢠EN61000-4-11, 30% 10 ms,
60% 100 ms, 100% 5000 ms
Perf Criteria A, B, B
⢠EN60950-1:2001, UL508, UL60950-1
|
▷ |