English
Language : 

8447140000 Datasheet, PDF (26/58 Pages) Weidmuller – Mini Coupler / Mini Conditioner
DC/DC Signal Conditioners
WAVEANALOG DC/DC 20 kHz
3-way-isolation
transmission frequency 20 kHz
analogue signal conditioning
cross-connectable voltage supply
via cross-connectors
CCC HF
0 ... 20 mA / 0 ... 20 mA
CCC HF
0 ... 20 mA / 4 ... 20 mA
CVC HF
0 ... 20 mA / 0 ... 10 V
Approvals:
Block diagram
Ordering data
Screw connection
Tension clamp connection
Input/output
Type
Cat. No.
WAS5 CCC HF 8447160000*
WAZ5 CCC HF 8447170000*
0 ... 20 mA / 0 ... 20 mA
Type
Cat. No.
WAS5 CCC HF 8447190000
WAZ5 CCC HF 8447200000
0 ... 20 mA / 4 ... 20 mA
Type
Cat. No.
WAS5 CVC HF 8447220000
WAZ5 CVC HF 8447230000
0 ... 20 mA / 0 ... 10 V
Technical data**
Input signal
Input current max
Input resistance
Output signal
Load resistance
Accuracy at Tu=23 °C
Temperature coefficient
Response time
Cut-off frequeny (-3 dB)
0 ... 20 mA
50 mA
50 Ω
0 ... 20 mA
≤ 500 Ω
< 0.2% of FS
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
0 ... 20 mA
50 mA
50 Ω
4 ... 20 mA
≤ 500 Ω
< 0.2% of FS
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
0 ... 20 mA
50 mA
50 Ω
0 ... 10 V
≥ 2 kΩ
< 0.2% of FS
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
General
Voltage supply
Power consumption
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
Dimensions L / H / W mm
Approvals
24 Vdc ±25% (18 ... 30 Vdc)
< 1.5 W at Iout = 20 mA
≤2A
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
24 Vdc ±25% (18 ... 30 Vdc)
< 1.5 W at Iout = 20 mA
≤2A
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
24 Vdc ±25% (18 ... 30 Vdc)
< 1.3 W at Iout = 5 mA
≤2A
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
Coordination of insulation according to EN 50178, 04/98
Rated voltage
Rated surge voltage
Overvoltage category
Contamination class
Clearance and creepage distance
Coupling capacity
Input / output to supply
Isolation voltage, voltage strength
Input/output to mounting rail
300 V
4 kV
III
2
≥ 3 mm
1 nF
4 kVeff / 1 min
Standards/specifications
EMC standards
EN 50178
EN 50081, EN 50082,
EN 55011
300 V
4 kV
III
2
≥ 3 mm
1 nF
4 kVeff / 1 min
EN 50178
EN 50081, EN 50082,
EN 55011
300 V
4 kV
III
2
≥ 3 mm
1 nF
4 kVeff / 1 min
EN 50178
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
Page 298 + 308
Page 298 + 308
Page 298 + 308
**TU = 23 °C single module