English
Language : 

1063280000 Datasheet, PDF (2/2 Pages) Weidmuller – BHZ 5.00/04/90LH BK/OR
Datasheet
CH20M
BHZ 5.00/04/90LH BK/OR
Technical data
Dimensions (1)
Length
Height
System parameters
14.6 mm
29 mm
Version
No. of connections
Protection class
Connectable conductors
Orange release lever
4
IP 20
Clamping range, min.
Conductor connection cross-section AWG,
min.
Solid, min. H05(07) V-U
Flexible, min. H05(07) V-K
with wire end ferrule, DIN 46228 pt 1, max.
with plastic collar ferrule, DIN 46228 pt 4,
max.
0.13 mm²
AWG 26
0.2 mm²
0.2 mm²
2.5 mm²
2.5 mm²
Material data
Flammability class UL 94
Colour
Highest continous operating temperature,
min.
V-0
black
-20 °C
Rating data to DIN IEC
Rated current, max. No. of poles (Tu=20°C) 10 A
Rated voltage for overvoltage class/pollution
severity II/2
400 V
Rated voltage at overvoltage category/
pollution degree III/3
250 V
Rated impulse withstand voltage for
overvoltage class/pollution severity III/2
4 kV
Approvals
Approvals institutes
Classifications
eClass 6.0
27-26-07-08
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-2083
www.weidmueller.com
Width
22.4 mm
Type of connection
Contact to terminal rail
Clamping yoke connection
No
Clamping range, max.
3.31 mm²
Conductor connection cross-section AWG,
max.
AWG 14
Solid, max. H05(07) V-U
2.5 mm²
w. wire end ferrule, DIN 46228 pt 1, min 0.25 mm²
w. plastic collar ferrule, DIN 46228 pt 4, min. 0.25 mm²
Insulating material
Contact surface
Highest continous operating temperature,
max.
PA 66 GV30
tinned
70 °C
Rated current, no. of poles (Tu=40°C), max. 9 A
Rated voltage for overvoltage class/pollution
severity III/2
320 V
Rated impulse withstand voltage for
overvoltage class/pollution severity II/2
4 kV
Rated impulse withstand voltage for
overvoltage class/pollution severity III/3
4 kV
Creation date July 23, 2010 10:54:41 PM CEST
Last update 28.05.2010 / We reserve the right to make technical changes.
2