English
Language : 

PSMBU152 Datasheet, PDF (1/3 Pages) Wall Industries,Inc. – AC/DC Open Frame Power Supplies
Wall Industries, Inc.
Rev A
PSMBU152 SERIES
150W Medical AC/DC Open Frame Power Supplies
Size:
5.00 x 3.00 x 1.44 inches
127.0 x 76.2 x 36.6 mm
FEATURES
 Class I
 RoHS Compliant
 Active Power Factor Correction
 5” x 3” x 1.44” Open Frame Package
 12VDC & 24VDC Single Outputs
 150 Watts Output Power
 Input to Output: 2MOPP
 Up to 89% High Efficiency
 Wide Input Voltage Range: 90~260VAC, 47~63Hz
 Over Voltage & Over Current Protection
 Meets FCC Part-18 Class B & CISPR-11 EN55011 Class B Emission Limits
 ANSI/AAMI ES 60601-1: 2005 (UL/cUL 3rd Edition) & EN 60601-1: 2006
(TUV/T-mark 3rd Edition)
 100% Burn-in Tested
DESCRIPTION
The PSMBU152 series of class I medical AC/DC switching power supplies provides 150 Watts of continuous output power in
a 5.00” x 3.00” x 1.44” open frame package. This series consists of 12VDC and 24VDC single output models with a wide input
voltage range of 90~260VAC. Some features include high efficiency up to 89%, active power factor correction, 2MOPP
insulation, and over current and over voltage protection. All models meet FCC Part-18 class B and CISPR-11 EN55011 class B
emission limits. This series also has ANSI/AAMI ES 60601-1: 2005 (UL/cUL 3rd edition) and EN 60601-1: 2006 (TUV/T-mark 3rd
edition) medical approvals. All models are RoHS compliant and have been 100% burn-in tested.
SPECIFICATIONS: PSMBU152 SERIES
All specifications are based on 25°C, Nominal Input Voltage, and Maximum Output Current unless otherwise noted.
We reserve the right to change specifications based on technological advances.
SPECIFICATION
TEST CONDITIONS
Min
Typ
Max
Unit
INPUT SPECIFICATIONS
Input Voltage
Input Frequency
Safety Approvals Input Voltage Range
Operating Input Voltage Range
100
90
240
260
VAC
47
63
Hz
Input Current
Inrush Current
No Load Power Consumption
Power Factor Correction
OUTPUT SPECIFICATIONS
Output Voltage
Line Regulation
Load Regulation
100VAC, full load
240VAC, full load
115VAC, full load, 25°C, cold start
230VAC, full load, 25°C, cold start
230VAC, no load
240VAC, full load
LL to HL, full load
230VAC
1.74
0.71
1.76
0.73
A
50
A
100
1.2
W
0.95
1
See Table
0.5
1
%
3
5
%
Output Power
Output Current
Ripple & Noise (peak to peak)
Hold-up Time
Start-up Time
Transient Response Time
Temperature Coefficient
90VAC, full load
110VAC, full load
100VAC, full load
100VAC, Full load to half load
0~50°C
20
-0.04
150
See Table
1
2
4
+0.04
W
%
ms
s
ms
%/°C
PROTECTION
Over Voltage Protection
Over Current Protection
112
132
%
110
150
%
GENERAL SPECIFICATIONS
Efficiency
Dielectric Withstanding Voltage
Isolation Resistance
Leakage Current
ENVIRONMENTAL SPECIFICATIONS
230VAC, full load
Primary to Secondary (2MOPP Insulation)
Primary to PE
Test Voltage = 500VDC
240VAC/60Hz
84
6990
2121
50
89
%
VDC
MΩ
0.25
mA
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
Operating Altitude
Cooling
MTBF
PHYSICAL SPECIFICATIONS
Weight
Dimensions (L x W x H)
Derating linearly from 100% Load at 50°C to 50% load at 70°C
MIL-HDBK-217F, 25°C
0
-40
0
0
100,000
+70
+85
95
95
3000
Free air convection
°C
°C
%
%
m
hours
14.82oz (420g)
5.00 x 3.00 x 1.44 inches (127.0 x 76.2 x 36.6 mm)
Input Connector
Output Connector
SAFETY & EMC
Safety Approvals
EMI Requirements for CISPR-11
EMI Requirements for FCC PART-18
220VAC
110VAC
See mechanical drawing
See mechanical drawing
ANSI/AAMI ES 60601-1: 2005 (UL/cUL 3rd edition); EN 60601-1:2006 (TUV/T-mark 3rd edition); CE
B
Class
B
Class
11/18/2013
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797
website: www.wallindustries.com • e-mail: sales@wallindustries.com
Page 1 of 3