46500 Datasheet, PDF (4/18 Pages) Vishay Siliconix – VDR Metal Oxide Varistors Standard
VDRS........E/2381 59. .....
VDR Metal Oxide Varistors Standard Vishay BCcomponents
ELECTRICAL DATA AND ORDERING INFORMATION
MAXIMUM
CONTINUOUS
VOLTAGE
RMS (2) DC
(V)
(V)
VOLTAGE (3)
at 1 mA
(V)
MAXIMUM
MAXIMUM
VOLTAGE
at STATED
CURRENT
MAXIMUM
ENERGY (4)
(10 x
1000 µs)
NON-REP.
TRANSIENT
CURRENT (5)
INRP
TYPICAL
CAP.
at 1 kHz
T
(max.)
(8 x 20 µs)
VI
(V) (A)
(J)
(A)
(pF) (mm)
E
(mm)
UL 1449
ED3
SPD
TYPE (8)
CATALOG
NUMBERS (1)
SAP (7)
12NC (6)
2381-
1000 5.0
18.0
400
40
6.0 3.0 ± 0.8 4
VDRS05C385xyE 592 x381y
1025 10.0 51.0
1200
95
6.0 3.0 ± 0.8 4
VDRS07H385xyE 593 x381y
385
505
620
1025 25.0 67.0
2500
180
6.6 3.2 ± 0.8 4
VDRS10P385xyE 594 x381y
1025 50.0 110.0
4500
280
6.6 3.2 ± 0.8 3
VDRS14T385xyE 595 x381y
1025 100.0 328.0
6500
570
7.7 3.5 ± 0.8 2 VDRS20W385ByE 596 x381y
1100 5.0
20.0
400
35
6.1 3.2 ± 0.8 4
VDRS05C420xyE 592 x421y
1120 10.0 56.0
1200
85
6.1 3.2 ± 0.8 4
VDRS07H420xyE 593 x421y
420
560
680
1120 25.0 73.0
2500
165
6.6 3.4 ± 0.8 4
VDRS10P420xyE 594 x421y
1120 50.0 120.0
4500
250
6.6 3.4 ± 0.8 3
VDRS14T420xyE 595 x421y
1120 100.0 344.0
6500
510
8.1 3.7 ± 0.8 2 VDRS20W420ByE 596 x421y
1200 5.0
21.0
400
30
6.4 3.6 ± 0.8 4
VDRS05C460xyE 592 x461y
1240 10.0 63.0
1200
75
6.4 3.6 ± 0.8 4
VDRS07H460xyE 593 x461y
460
615
750
1240 25.0 82.0
2500
150
6.8 3.8 ± 0.8 4
VDRS10P460xyE 594 x461y
1240 50.0 135.0
4500
225
6.8 3.8 ± 0.8 3
VDRS14T460xyE 595 x461y
1240 100.0 360.0
6500
460
8.5 4.1 ± 0.8 2 VDRS20W460ByE 596 x461y
1355 25.0 89.0
2500
135
7.2 4.1 ± 0.8 4
VDRS10P510xyE 594 x511y
510
670
820
1355 50.0 145.0
4500
220
7.2 4.1 ± 0.8 3
VDRS14T510xyE 595 x511y
1355 100.0 376.0
6500
450
8.9 4.4 ± 0.8 2 VDRS20W510ByE 596 x511y
1500 25.0 98.0
2500
120
7.9 4.5 ± 0.8 4
VDRS10P550xyE 594 x551y
550
745
910
1500 50.0 160.0
4500
180
7.9 4.5 ± 0.8 3
VDRS14T550xyE 595 x551y
1500 100.0 408.0
6500
370
9.5 4.9 ± 0.8 2 VDRS20W550ByE 596 x551y
625
825
1000 1650 100.0 448.0
6500
320 10.1 5.3 ± 0.8 2 VDRS20W625ByE 596 x621y
680
895
1100 1815 100.0 496.0
6500
270 10.6 5.8 ± 0.8 2 VDRS20W680ByE 596 x681y
Notes
(1) The products are certified according to (c)UL (E332800), VDE (40002622) and CSA (219883)
(2) The sinusoidal voltage is assumed as the normal operating condition. If a non-sinusoidal voltage is present, type selection should be based
on multiplying the peak voltage by a factor of 0.707.
(3) The voltage measured at 1 mA meets the requirements of IEC 61051.
The tolerance on the voltage at 1 mA is ± 10 %.
(4) High energy surges are generally of longer duration. The maximum energy for one pulse of 10 x 1000 µs is given as a reference for longer
duration pulses. This pulse can be characterised by peak current (Ip) and pulse width t2 (virtual time of half Ip value, following IEC 60060-2,
section 6 ). If Vp is the clamping voltage corresponding to Ip, the energy absorbed in the varistor is determined by the formula:
E = K x Vp x Ip x t2
where:
a) K is dependent on the value of t2 when the value of t1 is between 8 µs and 10 µs; see Peak Current as a Function of Pulse Width drawing.
(5) A current wave of 8 x 20 µs is used as a standard for pulse current and clamping voltage ratings. The maximum non-repetitive transient current
is given for one pulse applied during the life of the component.
(6) For composition of the 12NC part number replace “x” and “y” by figures from the sections “Varistors in Bulk”, “Varistors on Tape in Ammopack”
and “Varistors on Tape on Reel”.
(7) For composition of the SAP part number:
Replace “x” by B for bulk type
Replace “y” by S for straight leads
T for tape and reel
F for straight leads with flange (bulk only)
A for tape and ammopack
G for straight leads with flange and H0 = 16 mm (tape and reel/ammo)
H for straight leads with flange and H0 = 18.25 mm (tape and reel/ammo)
K for kinked leads (bulk only)
L for kinked leads with H0 = 16 mm (tape and reel/ammo)
M for kinked leads with H0 = 18.25 mm (tape and reel/ammo)
(8) All varistors are recognized under VZAC2 surge protective devices, components type 4 as specified in UL 1449 edition 3. The parts with
indication type 2 or 3 SPD's, are tested and certified to be used in type 2 or 3 SPD applications. The final acceptance of the component is
dependent upon its installation and use in complete equipment submitted to underwriters laboratories Inc.
Document Number: 29081
Revision: 07-Jun-10
For technical questions, contact: nlr@vishay.com