CTA400-0001-01 Datasheet, PDF (1/2 Pages) II-VI Marlow, Inc. – Air to Air TE Exchanger Standard Product
TECHNICAL DATA SHEET
Climatherm 400 Series
Air to Air TE Exchanger Standard Product
RoHS EU Compliant
MECHANICAL CHARACTERISTICS
TYPICAL PERFORMANCE VALUES
Specifications
Weight (kg)
5.5
Overtemp Thermostat 100°C ± 5°C (Both Sinks)
Operating Temp
-10°C to 60°C
Color
White
Blue
Red
Black
Electrical Connections
PIN #
Description
1
TEC “+”
2
TEC “-”
3
Fans “+”
4
Fans “-”
Plug
Socket
PIN Plug
PIN Socket
Connectors
Tyco P/N 480702-0
Tyco P/N 480703-0
Tyco P/N 350547-1
Tyco P/N 350550-1
Voltage Current
(nom/max) (nom/max)
CTA400-0001-XX 24/28
48/56
14/16
7/8
CTA400-0004-XX 24/28 11/12
48/56 5.6/6.5
Cooling
power
@ 0 dT
W
246
246
248
248
Performance
COP Curve
0.71
A
0.71
A
0.92
B
0.92
B
IP55 RATED FANS
ORDERING OPTIONS
Model Number
CTA400-0001-01
CTA400-0001-02
CTA400-0001-03
CTA400-0001-04
Description
24V, Hot Side Wiring
24V, Cold Side Wiring
48V, Hot Side Wiring
48V, Cold Side Wiring
CTA400-0004-01
CTA400-0004-02
CTA400-0004-03
CTA400-0004-04
24V, Hot Side Wiring
24V, Cold Side Wiring
48V, Hot Side Wiring
48V, Cold Side Wiring
AVAILABLE MODIFICATIONS
For information regarding additional ordering options
available, please contact a Marlow engineering representative.
For customer support or general questions please contact a local office or visit our website at www.marlow.com.
DOC # 102-0409 REV B - PAGE 1 OF 2