MODULE SPECIFIC OPERATING SPECIFICATIONS
24 Vout, 500 W (e.g. V150A24C500BL)
Parameter
Efficiency
Ripple and noise
Output OVP setpoint
Dissipation, standby
Load regulation
Load Current
Current limit
Short circuit current
Min
Typ
87.5
88.5
160
27.1
28.1
16.6
±0.02
0
21.2
23.9
14.5
23.9
24 Vout, 400 W (e.g. V150A24C400BL)
Parameter
Efficiency
Ripple and noise
Output OVP setpoint
Dissipation, standby
Load regulation
Load Current
Current limit
Short circuit current
Min
Typ
87
88.3
200
27.1
28.1
12.9
±0.02
0
17
19.2
11.6
19.2
28 Vout, 500 W (e.g. V150A28C500BL)
Parameter
Efficiency
Ripple and noise
Output OVP setpoint
Dissipation, standby
Load regulation
Load Current
Current limit
Short circuit current
Min
Typ
88.1
89.3
200
31.5
32.7
14.5
±0.02
0
18.2
20.6
12.5
20.6
28 Vout, 400 W (e.g. V150A28C400BL)
Parameter
Efficiency
Ripple and noise
Output OVP setpoint
Dissipation, standby
Load regulation
Load Current
Current limit
Short circuit current
Min
Typ
88
89.4
350
31.5
32.7
10
±0.02
0
14.5
16.4
10
16.4
36 Vout, 500 W (e.g. V150A36C500BL)
Parameter
Efficiency
Ripple and noise
Output OVP setpoint
Dissipation, standby
Load regulation
Load Current
Current limit
Short circuit current
Min
Typ
88
89
200
40.4
41.9
16.7
±0.02
0
14.1
16
9.73
16
Max
200
29.1
18
±0.2
20.83
28.1
28.1
Max
250
29.1
14
±0.2
16.67
22.6
22.6
Max
250
33.9
15.4
±0.2
17.86
24.2
24.2
Max
438
33.9
11.7
±0.2
14.29
19.4
19.4
Max
250
43.4
17.8
±0.2
13.89
18.8
18.8
Unit
%
mV
Volts
Watts
%
Amps
Amps
Amps
Unit
%
mV
Volts
Watts
%
Amps
Amps
Amps
Unit
%
mV
Volts
Watts
%
Amps
Amps
Amps
Unit
%
mV
Volts
Watts
%
Amps
Amps
Amps
Unit
%
mV
Volts
Watts
%
Amps
Amps
Amps
Notes
Nominal input; full load; 25°C
p-p; Nominal input; full load; 20 MHz bandwith
25°C; recycle input voltage to restart (>100 ms off)
No load
No load to full load; nominal input
Output voltage 95% of nominal
Output voltage <250 mV
Notes
Nominal input; full load; 25°C
p-p; Nominal input; full load; 20 MHz bandwith
25°C; recycle input voltage to restart (>100 ms off)
No load
No load to full load; nominal input
Output voltage 95% of nominal
Output voltage <250 mV
Notes
Nominal input; full load; 25°C
p-p; Nominal input; full load; 20 MHz bandwith
25°C; recycle input voltage to restart (>100 ms off)
No load
No load to full load; nominal input
Output voltage 95% of nominal
Output voltage <250 mV
Notes
Nominal input; full load; 25°C
p-p; Nominal input; full load; 20 MHz bandwith
25°C; recycle input voltage to restart (>100 ms off)
No load
No load to full load; nominal input
Output voltage 95% of nominal
Output voltage <250 mV
Notes
Nominal input; full load; 25°C
p-p; Nominal input; full load; 20 MHz bandwith
25°C; recycle input voltage to restart (>100 ms off)
No load
No load to full load; nominal input
Output voltage 95% of nominal
Output voltage <250 mV
Vicor Corp. Tel: 800-735-6200, 978-470-2900 Fax: 978-475-6715
150V Maxi Family
Set your site on VICOR at vicorpower.com
Rev. 2.0
Page 6 of 13