English
Language : 

BC384A480T033FP Datasheet, PDF (4/16 Pages) Vicor Corporation – BCM Bus Converter
SPECIFICATIONS (CONT.)
PRELIMINARY DATASHEET
Specifications apply over all line and load conditions unless otherwise noted; Boldface specifications apply over the temperature range
of -40°C < TC < 100°C (T-Grade); All other specifications are at TC = 25ºC unless otherwise noted
Electrical Characteristics (Continued)
Attribute
Symbol
Conditions / Notes
Min
Typ
Max
Unit
TM
TM accuracy
TM Gain
TM Source Current
TM Internal Resistance
External TM Capacitance
TM Voltage Ripple
PROTECTION
Negative going OVLO
Positive going OVLO
Negative going UVLO
Positive going UVLO
Output Overcurrent Trip
Short Circuit Protection
Trip Current
Short Circuit Protection
Response Time
Thermal Shutdown
Junction setpoint
ACTM
ATM
ITM
RTM_SNK
CTM
VTM_PP
CTM = 0 µF, VIN = 400 V, POUT = 325 W
VIN_OVLO-
VIN_OVLO+
VIN_UVLO-
VIN_UVLO+
IOCP
ISCP
VIN = 384 V, 25°C
TSCP
TJ_OTP
-5
+5
ºC
10
mV/°C
100
uA
25
40
50
kΩ
50
pF
200
400
500
mV
400
420
430
V
420
430
440
V
270
285
304
V
290
310
330
V
9
11
14
A
14
A
1.2
us
125
130
135
°C
GENERAL SPECIFICATION
Isolation Voltage (hipot)
Working Voltage (In – Out)
Isolation Capacitance
Isolation Resistance
MTBF
Agency Approvals/Standards
VHIPOT
VWORKING
CIN_OUT
RIN_OUT
Unpowered unit
MIL HDBK 217F, 25° C, GB
cTUVus
CE Mark
4242
V
500
V
500
660
800
pF
10
MΩ
4.2
Mhrs
Bus Converter Module
BC384A480T033FP
vicorpower.com
Rev. 1.0
Page 4 of 16