English
Language : 

IB050E120T40N1-00 Datasheet, PDF (3/13 Pages) Vicor Corporation – 4:1 Intermediate Bus Converter Module: Up to 500 W Output
SPECIFICATIONS (CONT.)
All specifications valid at 48 VIN , 100% rated load and 25°C ambient, unless otherwise indicated.
Electrical Characteristics (Continued)
Attribute
Symbol
Conditions / Notes
Min
Typ
Max
Unit
OUTPUT (Continued)
Efficiency
50% load
Full load
Internal output inductance
Internal output capacitance
Load capacitance
Output OVP set point
Output voltage ripple
Output Overload protection threshold
Over current protection time constant
Short circuit current response time
Switching frequency
Transient Response
Voltage overshoot
Response time
VIN step
Pre-bias voltage
See figures 1,2 and 3.
97.4
97.8
%
See figures 1,2 and 3.
97.0
97.4
%
1.6
nH
55
µF
0
3000
µF
Module will shutdown
16.2
Vdc
20 MHz bandwidth, using test circuit in
Figure 23
60
150
mVp-p
Of Iout max., will not shutdown when started
into max Cout; and 15% load
105
Auto restart with duty cycle <10%
150
%
1.2
ms
1.5
µs
1.0
MHz
25% load step; 1A /µS; See Figures 13 & 14
See Figures 13 & 14
5 V step in 1 µS within Vin operating range
Unit will start up
into pre-bias voltage on output
0
100
mV
1
µS
1.25
V
15
Vdc
General Characteristics
Attribute
MTBF
Service life
Over temperature shut down
Dielectric withstand
Insulation resistance
Mechanical
Weight
Length
Width
Height above customer board
Clearance to customer board
Agency approvals
Altitude, operating
Relative humidity, Operating
RoHS compliance
Conditions: 25°C case, 75% rated load and specified input voltage range unless otherwise specified.
Symbol
Conditions / Notes
Min
Typ
Max
Unit
Calculated per Telcordia SR-332, 40°C
Calculated at 30°C
TJ ; Converter will reset when over
temperature condition is removed
Input to output
Input to output
1.0
7
125
130
2,250
30
Mhrs
Years
135
°C
Vdc
MΩ
From lowest component on IBC
UL/cUL60950-1, EN60950-1, IEC60950-1
Low voltage directive (CE Mark)
Derate operating temp 1°C
per 1,000 feet above sea level
Non condensing
Compatible with RoHS directive 2002/95/EC
0.71 / 20.3
2.30 /58.4
0.9 / 22.9
0.38 /9.5
0.12/ 0.30
cTUVus
CE
-500
10
10,000
90
oz/g
in / mm
in / mm
in / mm
in / mm
Feet
%
VI BRICK IBC Module
IB050E120T40N1-00
vicorpower.com
Rev. 1.4
Page 3 of 13