English
Language : 

SU2200RTXL2UA_15 Datasheet, PDF (5/6 Pages) Tripp Lite. All Rights Reserved – SmartOnline 110-120V 2.2kVA 1.6kW On-Line Double-Conversion UPS, Extended Run, SNMP,Webcard, 2U Rack/Tower, USB, DB9 Serial
Cooling Method
UPS Housing Material
Fan
Steel
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
812.9
AC Economy Mode BTU / Hr. (Full
Load)
347.2
Battery Mode BTU / Hr. (Full Load) 885.6
AC Mode Efficiency Rating (100%
Load)
87%
AC Economy Mode Efficiency Rating
(100% Load)
94%
Audible Noise
< 45dB at 1m
COMMUNICATIONS
Communications Interface
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure
communications
PowerAlert Software
Included
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
No transfer time (0 ms.) in online, double-conversion mode
80V (100% load), 65V ( <70% load)
150
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS Features
Green Energy-Saving Features
Cold-start operation supported
Automatic inverter bypass; Hot swappable batteries
High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy
mode operation
CERTIFICATIONS
5/6