English
Language : 

SU80KX Datasheet, PDF (4/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 80kVA Modular 3-Phase UPS System,On-line Double-Conversion International UPS (not expandable to 120kVA)
UPS Power Module Weight (kg)
244.3
UPS Shipping Dimensions (hwd / in.) 55 x 28.5 x 42.5
UPS Shipping Dimensions (hwd /
cm)
139.7 x 72.4 x 108
Shipping Weight (lbs.)
687.8
Shipping Weight (kg)
312.3
Cooling Method
Fans
UPS Housing Material
Steel
ENVIRONMENTAL
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC Mode BTU / Hr. (Full Load)
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
14000
COMMUNICATIONS
Communications Interface
PowerAlert Software
Communications Cable
DB9 Serial; Slot for SNMP/Web interface
Included
DB9 cabling included
LINE / BATTERY TRANSFER
Transfer Time
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
No transfer time (0 ms.) in online, double-conversion mode
Maintains continuous operation without using battery power during brownout/undervoltage conditions to 173-300V
AC (3-phase, 4-wire, wye). Below this point, output is maintained utilizing reserve battery power
Maintains continuous operation without using battery power during overvoltages to 276-477V AC (3-phase, 4-wire,
wye), reducing output within 1% of nominal. Above this point, output is maintained utilizing reserve battery power
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS Features
Green Energy-Saving Features
Cold-start operation supported
Automatic inverter bypass; Hot swappable batteries
High efficiency economy mode operation; Schedulable daily hours of economy mode operation
WARRANTY
Product Warranty Period
(International)
Product Warranty Period (Mexico)
2-year limited warranty
1-year limited warranty