English
Language : 

SU80KX2 Datasheet, PDF (3/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 80kVA Modular 3-Phase UPS System,On-line Double-Conversion International UPS (expandable to 120kVA)
INPUT
Rated input current (Maximum Load) 103A (220/380), 99A (230/400), 95A (240/415)
Nominal Input Voltage(s) Supported 220/380V (3ph wye); 230/400V (3ph wye); 240/415V (3ph wye)
Nominal Input Voltage Description 3-Phase Wye, 4 wire (L1, L2, L3, N, G); Less than 4% input harmonic distortion (THDi)
UPS Input Connection Type
Hardwire
Input Phase
3-Phase
BATTERY
Expandable Battery Runtime
External Battery Pack Compatibility
Expandable Runtime Description
DC System Voltage (VDC)
Battery Replacement Description
Battery set sold separate
BP480V103 ; BP480V140 ; BP480V55 ; BP480V78 ; BP480V200 ; BP480V300 ; BP480V400 ; BP480V500
External battery pack wiring is contractor supplied
+/- 240VDC
Hot-swappable, replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Online, double-conversion power conditioning
Maintains continuous operation without using battery power during overvoltages to 276-477 (3-phase, 4-wire, wye),
reducing output within 1% of nominal
Maintains continuous operation without using battery power during brownout/undervoltage conditions to 173-300
(3-phase, 4-wire, wye)
USER INTERFACE, ALERTS & CONTROLS
Switches
ON button turns UPS inverter on. OFF button turns UPS inverter off. LCD Display Control Buttons browse through
and select items displayed on LCD screen. EPO (Emergency Power Off) button turns UPS output off and disables
Bypass output
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm
Alarms signal a variety of operational conditions: low-battery, overload, shutdown, bypass and more
LED Indicators
4-LED Display: Displays normal AC input, on battery power, bypass input and fault conditions
SURGE / NOISE SUPPRESSION
EMI / RFI AC Noise Suppression
AC Suppression Joule Rating
AC Suppression Response Time
Yes
5960
Instantaneous
PHYSICAL
Installation Form Factors Supported
with Included Accessories
Primary Form Factor
Tower
Tower
3/5