English
Language : 

SMART3000RMXL2U Datasheet, PDF (3/5 Pages) Tripp Lite. All Rights Reserved – SmartPro 120V 3kVA 2.88kW Line-Interactive Sine Wave UPS, Extended Run, SNMP, Webcard, 2U Rack-Tower, LCD, USB, DB9 Serial
UPS Input Cord Length (ft.)
UPS Input Cord Length (m)
Recommended Electrical Service
Input Phase
10
3
30A 120V
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
Expandable Battery Runtime
External Battery Pack Compatibility
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
3 min. (2880w)
10 min. (1440w)
Extended runtime supported via optional external battery packs
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible)
48
Less than 5 hours from 10 to 90% (typical, full load discharge)
RBC58-2U
Front panel battery access door
Hot-swappable, replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Severe Undervoltage Correction
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Input voltages between 127 and 145 are reduced by 12%
Input voltages between 108 and 96 are boosted by 12%
Input voltages between 83 and 95 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating
data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual
for detailed LCD configuration and monitoring options)
Switches
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
EMI / RFI AC Noise Suppression
AC Suppression Response Time
570
Yes
Instantaneous
PHYSICAL
3/5