Output Receptacles
(4) 5-15R; (4) 5-15/20R
Load Management Receptacles
Three switchable single-outlet 5-15R load banks
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 16A
Nominal Input Voltage(s) Supported 120V AC
UPS Input Connection Type
5-20P
Input Circuit Breakers
20A
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3
Recommended Electrical Service
20A 120V
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
Expandable Battery Runtime
External Battery Pack Compatibility
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
11 min. (1900w)
28 min. (950w)
Extended runtime supported via optional external battery packs
BP48V24-2U (limit 1); BP48V48RT4U (multi-pack compatible); BP48V27-2US (multi-pack compatible)
48
Less than 3.6 hours from 10% to 90% (typical, full load discharge)
RBC94-2U (quantity 2)
Front panel battery access door
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Severe Undervoltage Correction
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Input voltages between 127 and 145 are reduced by 12%
Input voltages between 96 and 108 are boosted by 12%
Input voltages between 83 and 95 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support
low/high charger settings