English
Language : 

SUINT1500RTXL2UA Datasheet, PDF (2/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 200-240V 1.5kVA 1.2kW On-Line Double-Conversion UPS, Extended Run, SNMP,Webcard, 2U Rack/Tower, USB, DB9 Serial
IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles
2 C13 to C14 output power cables included
Standard internal battery set provides 12 minutes runtime at half load and 4.5 minutes runtime at full load
Optional BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack compatible) and BP48V27-2US (multi-pack compatible) external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Highly efficient operation in optional Economy Mode setting, saving BTU heat output and energy costs.
Innovative design makes unit adaptable to rackmount, tower, or stacking applications
Uses only 2 rack spaces (2U) in standard 19-inch rack
Optional 2-9USTAND kit enables upright tower placement
Optional 2POSTRMKITWM enables 2-post rackmount or wallmount installation
Supports simultaneous communications via built-in USB port, DB9 serial port and SNMPWEBCARD slot
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Slot for optional SNMP/web card (Part Number: SNMPWEBCARD)
PowerAlert unattended shutdown software and communications cabling included
Compatible with Tripp Lite's WatchDog software
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Optional PDUBHV10 bypass PDU enables hot-swappable UPS replacement with no disruption to connected equipment
Built-in Emergency Power Off (EPO) interface with cable
Single-line tel/DSL or Ethernet network surge suppression
Integrated 2-bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each bank has 3 outlets)
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output kVA Capacity (kVA)
Output Watt Capacity (Watts)
Output kW Capacity (kW)
Power Factor
Crest Factor
Nominal Output Voltage(s)
Supported
Nominal Voltage Details
Frequency Compatibility
Frequency Compatibility Details
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation
(Economy Line Mode)
Output Voltage Regulation (Battery
Mode)
1500
1.5
1200
1.2
0.8
3:1
200V; 220V; 230V; 240V
230V default
50 / 60 Hz
Output frequency matches input nominal on startup, defaults to 50 Hz on cold-start
+/- 2%
+/- 10%
+/- 2%
2/5