English
Language : 

SU30K33_15 Datasheet, PDF (2/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 3-Phase In-Out 120-208V 30kVA 24kW On-Line Double-Conversion UPS, Extended Run,SNMP, Webcard, Tower, DB9 Serial, Hardwire
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
30,000VA/24,000 watt power capacity with 3-phase, hardwire 120/208V AC input/output connections
Features a wide input voltage correction range: 96 - 144/166 - 250V AC
Included internal batteries provide 13 minutes runtime at half load (12,000 watts) and 5 minutes runtime at full load (24,000 watts)
3:1 crest factor safely supports a variety of equipment, even those with wildly-fluctuating power demands
Extend runtime by installing an optional internal battery pack (model # SURBC2030) through the front panel access door. SU30K3/3 includes 3 internal
battery packs and accepts 1 additional internal battery pack. A standalone battery module compartment with a 4 battery pack capacity and daisy-chain
capability (model # SUBF2030) is available to further extend runtime.
3 communication ports (RS-232, contact closure and AS-400)
Slot for optional SNMP card (model # SNMPWEBCARD)
Manual bypass switch as well as an automatic bypass function ensures 100% availability of connected equipment by safely passing through AC power
when the UPS system requires maintenance
Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval
Emergency Power Off button turns UPS output OFF and disables Bypass output
PowerAlert Universal UPS Power Management Software and 6 ft. communication cable included
Start-up service program is recommended to enhance the reliability of the installation
Built-in Emergency Power Off (EPO) interface supports remote emergency shutdown in large facilities
Combination LED/LCD display
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
30000
Output kVA Capacity (kVA)
30
Output Watt Capacity (Watts)
24000
Output kW Capacity (kW)
24
Power Factor
0.8
Crest Factor
3:1
Nominal Output Voltage(s)
Supported
120/208V; 3-Phase Wye
Frequency Compatibility
50 / 60 Hz
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles
Hardwire
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave