English
Language : 

SU1500RTXL2UA_15 Datasheet, PDF (2/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 100-120V 1.5kVA 1.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower,USB, DB9 Serial
Compact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 in.
Ships with all mounting accessories for 4-post rackmount installation
Optional 2POSTRMKITWM enables 2-post rackmount or wallmount installation
Optional 2-9USTAND accessory enables small-footprint upright tower placement
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure and SNMPWEBCARD slot
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number
of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery
capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS nominal voltage adjustment
and UPS line to battery power voltage setpoints
Built-in Emergency Power Off (EPO) interface with cable
NEMA 5-15P input plug; NEMA 5-15R output receptacles
Integrated 2-bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (bank one has 2 outlets,
bank two has 4 outlets)
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations; no time-consuming connection of internal batteries by user required
Single-line tel/DSL or network Ethernet surge suppression
$250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only)
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output kVA Capacity (kVA)
Output Watt Capacity (Watts)
Output kW Capacity (kW)
Power Factor
Crest Factor
Nominal Output Voltage(s)
Supported
Nominal Voltage Details
Frequency Compatibility
Frequency Compatibility Details
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation
(Economy Line Mode)
Output Voltage Regulation (Battery
Mode)
1500
1.5
1200
1.2
0.8
3:1
100V; 110V; 120V
120V default
50 / 60 Hz
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
+/- 2%
+/- 10%
+/- 2%