PDU3MV6L2130A Datasheet, PDF (2/3 Pages) Tripp Lite. All Rights Reserved – 3-Phase Metered PDU, 8.6 kW, 45 208V outlets (36 C13, 9 C19), 6 ft NEMA L21-30P input connection,TAA Compliant
OUTPUT
Output Capacity Details
Frequency Compatibility
Output Receptacles
Output Nominal Voltage
Overload Protection
Outlet Type
INPUT
PDU Input Voltage
Maximum Input Amps
PDU Plug Type
Input Cord Length (ft.)
Input Cord Length (m)
Input Phase
PHYSICAL
Shipping Dimensions (hwd / in.)
Shipping Dimensions (hwd / cm)
Shipping Weight (lbs.)
Shipping Weight (kg)
Unit Dimensions (hwd / in.)
Unit Dimensions (hwd / cm)
Unit Weight (lbs.)
Unit Weight (kg)
Material of Construction
Form Factors Supported
PDU Form Factor
ENVIRONMENTAL
Storage Temperature Range
Relative Humidity
Operating Elevation (ft.)
Operating Elevation (m)
8.6kW total capacity; 13.8A max per output phase; Phase L1-L2 feeds black C13 & C19 outlets; Phase L2-L3 feeds
dark-gray C13 & C19 outlets; Phase L3-L1 feeds light-gray C13 & C19 outlets
50 / 60 Hz
(36) C13; (9) C19
208V single phase
3 20A double-pole circuit breakers (1 per output phase)
IEC-C13, IEC-C19
208
24
NEMA L21-30P
6
1.83
3-Phase
75.9 x 9.7 x 7.1
192.8 x 24.6 x 18.0
22.72
10.31
70 x 2.65 x 2.2
177.8 x 6.73 x 5.6
13.5
6.1
Aluminum
Vertical rackmount installation supported with included mounting brackets; supports toolless mounting in
button-mount compatible racks
Vertical (0U)
-15C - 50C / 5 - 122F
5-95% non-condensing
0-10,000 ft
0-3000m
2/3