SmartOnline 200-240V 6kVA 5.4kW On-Line
Double-Conversion UPS, Extended Run, SNMP,
Webcard, 4U Rack/Tower, USB, DB9 Serial, Bypass
Switch
Highlights
6kVA / 6000VA / 5400W on-line
double-conversion UPS; 0.9
power factor
Included maintenance bypass
MODEL NUMBER: SU6000RT4UHVG
switch enables live replacement
of UPS with zero downtime
200/208/220/230/240V 50/60Hz
output; High efficiency economy
mode option
4U Rack/Tower compatible;
Hot-swap power and battery
modules
USB, RS232 & EPO ports;
SNMP/WEB and contact-closure
card options
Front panel LEDs with detailed
LCD monitoring and control
screen
Expandable runtime with optional
Description
Tripp Lite SU6000RT4UHVG 6000VA / 6kVA / 5400 watt on-line, double-conversion UPS system offers complete
power protection for critical server, network and telecommunications equipment in a single 4U rack/tower
compatible housing. Full-time active power conditioning provides clean, continuous dual-conversion AC output
external battery packs
Hardwire input (3 wire) with
optional cordsets available; C19
outlets
free of voltage fluctuations, power interruptions and line noise. Fault-tolerant auto-bypass prevents unexpected
service interruptions during UPS overload or internal fault conditions. Detachable back panel PDU with manual
bypass switch supports hot-swappable whole UPS replacement with no interruption to connected equipment.
Single all-in-one rack / tower housing installs in only 4 rack spaces (4U) with a maximum installed depth of only
20.7 in. / 52.6cm. Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal
during brownouts as low 100V and overvoltages as high as 300V. Expandable runtime is supported with optional
BP192V12-3U external battery packs. Battery independent restart ensures automatic UPS power-up without
user interaction after lengthy power outages, even when batteries are expired and require replacement.
Double-conversion operation converts raw input from AC to DC, then re-synthesizes output power back to
perfect sine wave AC with enhanced protection from harmonic distortion, fast electrical impulses and other
hard-to-solve power problems not addressed by other UPS types. Highly efficient operation in optional economy
mode significantly reduces BTU heat output and operating energy costs. Network-grade AC surge and noise
Package Includes
SU6000RT4UHVPM
Hot-swappable UPS Power
Module
SUPDMB6KIEC Detachable
PDU with Maintenance Bypass
Switch
PowerAlert Software CD
1 x 6-ft. USB Cable
1 x 6-ft. DB9 Cable
4-Post Rackmount Hardware
suppression. Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces. Optional
SNMP/Web and contact-closure communications card accessories available. HID-compliant USB interface enables integration with built-in power management
and auto shutdown features of Windows and Mac OS X. Included PowerAlert monitoring software offers detailed site power and UPS updates with support for
safe auto-shutdown of connected systems as UPS batteries become depleted. Included software packages include PowerAlert Local, PowerAlert Network
Shutdown Agent and PowerAlert Network Management System for complete support for a wide variety of application types. Supports Emergency Power Off
(EPO) via built-in interface. Front panel LEDs and LCD readout with scroll controls support front-panel visual monitoring of all major UPS for a variety of control
options to support advanced UPS settings and configurations. LED / LCD display panel rotates for viewing in rackmount or tower configurations. Hardwire
input and 4 C19 outlets. Support for optional North American and International cordsets. External battery packs are field replaceable and hot swappable.