SU40KX Datasheet, PDF (1/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 40kVA Modular 3-Phase UPS System,On-line Double-Conversion International UPS
SmartOnline 40kVA Modular 3-Phase UPS System,
On-line Double-Conversion International UPS
Highlights
40,000 VA (40kVA) 3-phase
tower UPS
MODEL NUMBER: SU40KX
N+1 redundant modular
architecture helps assure 100%
availability
1+1 parallel capability allows for
system redundancy or increased
capacity
Low THDi reduces installation
costs by permitting 1:1 generator
sizing
3-phase hardwire (220/380V,
230/400V or 240/415V AC,
3-phase, 4-wire + ground, wye)
input/output
IGBT technology and zero
transfer time, on-line
Description
double-conversion operation
Tripp Lite's SU40KX (40kVA) SmartOnline Modular 3-Phase Intelligent, True On-Line UPS System provides
Runtime is expandable via
100% system availability with N+1 modular architecture and 1+1 parallel capability. In N+1 configuration, the
external battery cabinet options
SU40KX provides two self-contained, redundant 20kVA power modules that can be hot-swapped (load remaining
powered) if maintenance is required. In 1+1 configuration , two SU40KX models connected in parallel can
provide fail-safe redundancy (two 40kVA models supporting a 40kVA load) or increased capacity (two 40kVA
models supporting an 80kVA load). Large capacity 40,000VA/32,000W UPS continually converts incoming AC
power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly
regulated, continuous sine wave output with zero transfer time assures compatibility with all equipment types.
Package Includes
SU40KX UPS System
PowerAlert Software
Instruction manual
Warranty information
High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology
produce less than 3% input total harmonic distortion (THDi). With low THDi, generators run cooler and last longer, allowing managers to save installation costs
by installing a generator with a capacity equal to the equipment load (1:1 ratio). Extremely efficient operation (up to 97%) saves money by lowering electricity
consumption. Hardwire input and output connections support a variety of permanent or PDU-style power connections. Frequency is 50 or 60 Hz
(auto-selectable). The SU40KX combines internal power and battery modules in a single small-footprint tower compartment. Typical half-load/full-load runtimes
are 13 min./5.5 min. Battery runtime can be extended with optional stand-alone hardwired external battery modules (Models BP480V26B and BP480V40C,
available separately). A manual bypass breaker and an automatic bypass function ensure 100% availability of connected equipment by safely passing through
AC power if the UPS requires maintenance.
Features
N+1 configuration: If maintenance is required, two self-contained, redundant 20kVA power modules can be hot-swapped with the load remaining powered
1+1 configuration: Two SU40KX can be connected in parallel to provide either fail-safe redundancy or increased capacity
High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology produce low input total harmonic distortion
(THDi)
Low THDi (less than 3%) reduces installation costs by allowing 1:1 generator sizing
Extremely efficient operation (up to 97%) saves money by reducing electricity consumption
True on-line, double-conversion UPS with IGBT technology provides pure sine wave AC output at all times
Maintains continuous operation with zero transfer time through blackouts, voltage fluctuations and surges
1/5