SU40K Datasheet, PDF (1/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 40kVA Modular 3-Phase UPS System,On-line Double-Conversion UPS for North America
SmartOnline 40kVA Modular 3-Phase UPS System,
On-line Double-Conversion UPS for North America
Highlights
40,000 VA (40kVA) tower UPS
with 2 hot-swappable power
MODEL NUMBER: SU40K
modules
N+1 redundant modular
architecture helps assure 100%
availability
1+1 parallel capability allows for
system redundancy or increased
capacity
Low THDi saves installation costs
by permitting 1:1 generator sizing
3-phase hardwire
(120/208VAC)input/output. Wide
input voltage correction range
(94-150V AC/163-260V AC)
On-line, double-conversion
operation with zero transfer time;
Description
IGBT technology; extremely
Tripp Lite's SU40K (40kVA) SmartOnline Modular 3-Phase Intelligent, True On-Line UPS System provides
efficient operation (up to 96%)
100% system availability with N+1 modular architecture and 1+1 parallel capability. In an N+1 configuration, the
SU40K provides two self-contained, redundant 20kVA power modules that can be hot-swapped (with the load
Runtime is expandable via
external battery cabinet options
powered) if maintenance is required. Connect two SU40K models in parallel (1+1 configuration) to provide
fail-safe redundancy (two 40kVA models supporting a 40kVA load) or to increase capacity (two 40kVA models
supporting an 80kVA load).
Package Includes
SU40K UPS System
PowerAlert Software and cabling
The SU40K provides mission-critical equipment with the highest level of power protection available. Large
capacity 40,000VA/32,000W UPS continually converts incoming AC power into filtered DC power, and then
resynthesizes it back into AC power with a pure sine wave. Perfectly regulated, continuous sine wave output with
zero transfer time assures compatibility with all equipment types. The SU40K's high input power factor, advanced
Parallel cable (for 1+1 operation)
Instruction manual and startup
checklist
Warranty information
IGBT inverter technology and Digital Signal Processor (DSP) technology produce less than 3% input Total
Harmonic Distortion (THDi). With low THDi, generators run cooler and last longer, allowing managers to save installation costs by installing a generator with a
capacity equal to the equipment load (1:1 ratio). Extremely efficient operation (up to 96%) saves money by lowering electricity consumption. Hardwire input
and output connections support a variety of permanent or PDU-style power connections. The SU40K features 120/208V AC, 3-phase, 4-wire (plus ground),
wye input and output. It also features a wide input voltage correction range: 94-150/163-260V AC. Frequency is 50 or 60 Hz (auto-selectable). The SU40K
combines internal power and battery components in a single small-footprint tower module. Typical half-load/full-load runtimes are 13 min./5.5 min. Battery
runtime can be extended with optional stand-alone hardwired external battery modules (Models BP480V26B and BP480V40C with matching battery cabinets,
available separately). Additional battery cabinets for extended runtime solutions also available; contact Tripp Lite for more information. A manual bypass
breaker and an automatic bypass function ensure 100% availability of connected equipment by safely passing through AC power if the UPS requires
maintenance. A built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single server.
An accessory slot accepts an optional internal SNMP card (Model SNMPWEBCARD) for remote shutdowns, reboots and more. Front panel combination
LCD/LED display alerts users to a variety of UPS operational modes and conditions. The LCD display includes a real-time event log screen with up to 500
events listed. A dynamic battery management screen optimizes battery function to lengthen service life and allows cold restart of the UPS during a prolonged
blackout to utilize its batteries for periodic system access or data retrieval. An Emergency Power Off button turns the UPS output OFF and disables Bypass