SU20KRT8 Datasheet, PDF (1/6 Pages) Tripp Lite. All Rights Reserved – SmartOnline 200-240V 20kVA 18kW On-Line Double-Conversion UPS, N+1, Extended Run,SNMP, Webcard, 12U Rack-Tower, USB, DB9 Serial,NEMA Outlets
SmartOnline 200-240V 20kVA 18kW On-Line
Double-Conversion UPS, N+1, Extended Run,
SNMP, Webcard, 12U Rack/Tower, USB, DB9 Serial,
NEMA Outlets
MODEL NUMBER: SU20KRT8
Highlights
20kVA / 20,000VA / 18,000W
on-line double-conversion UPS;
0.9 power factor
200/208/220/230/240V 50/60Hz
output; 96% Efficient
Economy-mode option
Hot-swap power and battery
modules, N+1 fault tolerance at
loads up to 10kVA
USB, RS232 & EPO ports;
support for SNMP/WEB and
contact-closure card options
Front panel LEDs with detailed
LCD monitoring and control
screen
Expandable runtime with optional
external battery packs
Hardwire input (3 wire); L6-20R
and L6-30R outlets
Description
Tripp Lite SU20KRT8 20,000VA / 20kVA / 18,000 watt online, double-conversion UPS system offers complete
power protection for critical server, network and telecommunications equipment in a 12U rack/tower
configuration. This system delivers complete N+1 redundancy when used at loads up to 10kVA, and
non-redundant operation at loads between 10 and 20kVA. Fault-tolerant auto-bypass prevents unexpected
service interruptions during UPS overload or internal fault conditions. Included parallel PDU with manual bypass
switching enables hot-swappable replacement of all major UPS system components in both N+1 and combined
operating modes. Enhanced availability, fault tolerance and simple hot-swap replacement options make this UPS
ideal for advanced networking applications in data centers, computer rooms, network closets and rugged
industrial locations.
Package Includes
Two SU10000RT3UPM UPS
power modules
Two BP240V10RT3U battery
packs
SUPDMB20K8 PDU with Bypass
switch
4-post rackmount installation kit
PowerAlert software and
complete cabling
Features
Tripp Lite SU20KRT8 20kVA, 20,000VA / 18,000 watt on-line, double-conversion UPS system in 12U total rack/tower configuration
Unique configuration offers 20kVA non-redundant operation and automatic N+1 redundancy at load levels of 10kVA and under
Included Parallel PDU with manual bypass switch enables hot-swap replacement of power modules at any supported load level
Hardwire input; 8 L6-20R & 2 L6-30R outlets
Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal
Supports 50/60Hz operation for worldwide frequency compatibility
Expandable runtime with optional external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Battery independent restart
Highly efficient economy mode option
Optional SNMPWEBCARD, RELAYIOCARD and RELAYIOMINI interface modules available (RELAYIOMINI requires removal of USB interface module)
Applications utilizing the optional network communications card require two SNMPWEBCARD accessories (install one per included power module)