SU20KRT1TF Datasheet, PDF (1/6 Pages) Tripp Lite. All Rights Reserved – SmartOnline 208-120V or 240-120V 20kVA 18kW, On-Line Double-Conversion UPS, N+1, Extended Run, SNMP, Webcard, 14U Rack-Tower, USB, DB9 Serial
SmartOnline 208/120V or 240/120V 20kVA 18kW,
On-Line Double-Conversion UPS, N+1, Extended
Run, SNMP, Webcard, 14U Rack/Tower, USB, DB9
Serial
MODEL NUMBER: SU20KRT-1TF
Highlights
20kVA / 20,000VA / 18,000W
on-line double-conversion UPS;
0.9 power factor
208/120V or 240/120V 60Hz
output; 96% Efficient
Economy-mode option
Hot-swap power and battery
modules, N+1 fault tolerance at
loads up to 10kVA
USB, RS232 & EPO ports;
support for SNMP/WEB and
contact-closure card options
Front panel LEDs with detailed
LCD monitoring and control
screen
Expandable runtime with optional
external battery packs
Hardwire input (3 wire); L6-30R,
C19, 5-15/20R & 5-15R outlets
Description
Package Includes
Tripp Lite SU20KRT-1TF 20,000VA / 20kVA / 18,000 watt online, double-conversion UPS system offers
complete power protection for critical server, network and telecommunications equipment in a 14U rack/tower
configuration. This system delivers complete N+1 redundancy when used at loads up to 10kVA, and
non-redundant operation at loads between 10 and 20kVA. Fault-tolerant auto-bypass prevents unexpected
service interruptions during UPS overload or internal fault conditions. Included parallel PDU with manual bypass
switching enables hot-swappable replacement of all major UPS system components in both N+1 and combined
operating modes. Enhanced availability, fault tolerance and simple hot-swap replacement options make this UPS
ideal for advanced networking applications in data centers, computer rooms, network closets and rugged
industrial locations.
Features
Tripp Lite SU20KRT-1TF 20kVA, 20,000VA / 18,000 watt on-line, double-conversion UPS system in 14U total
Two SU10000RT3UPM UPS
power modules
Two BP240V10RT3U battery
packs
One SU6000XFMR2U 208/240V
to 120V transformer
SUPDMB20K parallel PDU with
Bypass switch
4-post rackmount installation kit
PowerAlert software and
complete cabling
rack/tower configuration
Unique configuration offers 20kVA non-redundant operation and automatic N+1 redundancy at load levels of 10kVA and under
Included Parallel PDU with manual bypass switch enables hot-swap replacement of power modules at any supported load level
Hardwire input; 2 L6-30R (208/240v), 8 C19 (208/240v), 8 5-15/20R (120v) and 4 5-15R (120v) outlets
Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V & 120V nominal
Expandable runtime with optional external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Battery independent restart
Highly efficient economy mode option
Optional SNMPWEBCARD, RELAYIOCARD and RELAYIOMINI interface modules available (RELAYIOMINI requires removal of USB interface module)
Applications utilizing the optional network communications card require two SNMPWEBCARD accessories (install one per included power module)