SU10000RT3UG Datasheet, PDF (1/6 Pages) Tripp Lite. All Rights Reserved – SmartOnline 200-240V 10kVA 9kW On-Line Double-Conversion UPS, Extended Run, SNMP,Webcard, 6U Rack-Tower, C19 Outlets
SmartOnline 200-240V 10kVA 9kW On-Line
Double-Conversion UPS, Extended Run, SNMP,
Webcard, 6U Rack/Tower, C19 Outlets
Highlights
Included maintenance bypass
switch enables live replacement
of UPS with zero downtime
MODEL NUMBER: SU10000RT3UG
10kVA / 10,000VA / 9000W
on-line double-conversion UPS;
0.9 power factor
200/208/220/230/240V 50/60Hz
output with economy mode option
6U Rack/Tower compatible;
Hot-swappable power and
battery modules
USB, RS232 & EPO ports;
support for SNMP/WEB and
contact-closure card options
Front panel LEDs with detailed
LCD monitoring and control
screen
Expandable runtime with optional
Description
Tripp Lite SU10000RT3UG 10,000VA / 10kVA / 9000 watt online, double-conversion UPS system offers
complete power protection for critical network applications. This system delivers online, double-conversion UPS
external battery packs
Hardwire input (3 wire); C19
outlets
protection with zero transfer time, suitable for advanced networking applications. Fault-tolerant auto-bypass
prevents unexpected service interruptions during UPS overload or internal fault conditions. Included detachable
PDU with manual bypass switch enables hot-swappable replacement of entire UPS power module with no
interruption to connected equipment. Enhanced availability, fault tolerance and simple hot-swap replacement
options make this UPS ideal for advanced networking applications in data centers, computer rooms, network
closets and rugged industrial locations.
Package Includes
SU10000RT3UPM 3U UPS
power module
BP240V10RT3U external battery
pack
Features
Tripp Lite SU10000RT3UG 10kVA / 10,000VA / 9000 watt on-line, double-conversion UPS system in 6U total
rack/tower configuration (3U UPS power module and 3U external battery pack)
Detachable PDU with manual bypass switch enables hot-swappable UPS power module replacement with no
interruption in output power to connected networking equipment
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
SUPDMB710IEC Detachable
PDU with manual bypass switch
Four post compatible rack rail kit
(2 sets)
PowerAlert software, complete
data cabling and user manual
Hardwire input; 6 C19 outlets
Maximum installed rack depth of only 32.5 in. / 82.6cm
Full-time active power conditioning provides clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise
Double-conversion operation converts raw input from AC to DC, then resynthesizes output power back to perfect sine wave AC with enhanced protection
from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types
Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal during brownouts as low 100V and overvoltages as high as
300V
Supports 50/60Hz operation for worldwide frequency compatibility
Expandable runtime is supported with optional BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH