PDUMH32HVATNET Datasheet, PDF (1/4 Pages) Tripp Lite. All Rights Reserved – TAA-Compliant 7.4kW Single-Phase ATS/Switched PDU, 230V Outlets (16 C13 & 2 C19), 2 IEC309 32A Blue Cords, 2U Rack-Mount
TAA-Compliant 7.4kW Single-Phase ATS/Switched
PDU, 230V Outlets (16 C13 & 2 C19), 2 IEC309 32A
Blue Cords, 2U Rack-Mount
MODEL NUMBER: PDUMH32HVATNET
Highlights
Single-phase IEC309 32A Blue
(2P+E) input and 230V output
16 C13 and 2 C19 switched
outlets in 2 load banks
Automatic transfer switching
within 1–5 ms
Ethernet network interface for
remote access
Digital LED display for real-time
status monitoring
Package Includes
PDUMH32HVATNET 7.4kW
Single-Phase 230V
ATS/Switched PDU
Rack-mounting brackets
Cord retention brackets
Cable ties
Description
Owner’s manual
The PDUMH32HVATNET 7.4kW Single-Phase 230V ATS/Switched PDU provides remote power monitoring and enables redundant power for network devices
with non-redundant power supply configurations. Ideal for data centers and server rooms, it mounts in 2U of space in EIA-standard racks and features 18
switched outlets(16 C13 and two C19) in two load banks, each bank protected by a 20A circuit breaker.
Dual 3-meter input cords with IEC309 32A Blue(2P+E) plugs connect to separate primary and secondary single-phase 230V power sources. The PDU
constantly evaluates the power quality of both input sources. Dynamic solid-state(TRIAC) automatic transfer switching allows the PDU to switch to the
secondary source within 1–5 milliseconds should the primary source fail or become unstable to ensure your connected equipment operates without
interruption.
Built-in Ethernet network interface allows remote access to the PDU for power monitoring, configuration, control and notifications via web browser, SSH, telnet
or SNMP. Provides real-time load/current data with billing-grade accuracy(+/- 1 percent). Supports user-programmable startup of outlets in any order or interval
to ensure network items are turned on in the proper sequence and reliably discovered. Digital LED display indicates power availability, voltage, source A/B
input status, output load and power factor, as well as temperature and humidity with the optional ENVIROSENSE module(sold separately).
Features
Primary and Secondary Inputs for Power Redundancy
Provides remote power monitoring and enables redundant power for network devices with non-redundant power supply configurations
Dual 3m input cords with IEC309 32A Blue(2P+E) plugs connect to separate primary and secondary single-phase power sources
Automatic Transfer Switching
Dynamic solid-state(TRIAC) automatic transfer switching
Switches to secondary power source if primary source fails or becomes unstable
1–5 ms transfer time ensures uninterrupted operation of connected equipment
Built-in processor monitors both sources and prevents switching if secondary source is unavailable or of lower quality than primary source