Electrical Specifications (@25C)
1. Maximum Power: 2500VA
2. Input Voltage: Series: 230VAC, 50/60Hz
Parallel: 115VAC, 50/60Hz
3. Output Voltage: Series: 230VAC CT @ 10.87A
Parallel: 115VAC @ 21.74.0A
4. Voltage Regulation: 2.5% TYP from full load to no load
5. Temperature Rise: 50°C TYP
6. Hipot: 4000VAC, Primary to Secondary
7. Efficiency: 97% TYP. @ full load
Construction:
The toroidal construction inherently helps reduce stray fields, increases efficiency
and minimizes size compared to traditional EI transformers. Built with Class B (130°)
insulation system.
Safety:
World Series Transformers are designed and manufactured to meet most
International Safety agency standards.
Agency File:
OD
UL: File E122529, UL 506
CE: EN 61558-1:2005, EN 61558-2-6:1995, Low Voltage Directive (LVD)
EN 6-000-6-6:2001+A11:2004, EN 55014-1:2000+A1:2001+A2:2002, EN
6100-6-1:2001, EN 55014-2:1997+A1:2001, Electromagnetic Compatibility (EMC)
RoHS
2002/95/EC
Dimensions (mm):
H
O.D.
MOUNTING
METAL
PLATE
BOLT FLAT
WASHER
112.0 208.0
H
Weight: 19.4Kg
Mounting:
Transformer is provided with one rubber, M8 x 120mm bolt, nut, spring and flat
washer.
Connections:
Transformer is provided with 12” (305mm) long, 0.50” (12.7mm) stripped and tinned,
stranded UL 1015 lead wire. Primaries are 14AWG, Secondaries are 14AWG.
Input1: Series – BLUE and BROWN, Jumper GRAY to VIOLET
Parallel – BLUE and BROWN, Jumper BLUE to VIOLET, GRAY to BROWN
Output1: Series – BLACK and YELLOW, Jumper RED to ORANGE
Parallel – BLACK and YELLOW, Jumper BLACK to ORANGE, RED to YELLOW
RoHS Compliance: As of manufacturing date February 2005, all standard products meet the
requirements of 2011/65/EU, known as the RoHS initiative.
SPRING
WASHER
P
R BLUE
I GRAY
M
VIOLET
A
RUBBER
NUT
PAD
S
E
BLACK C
O
RED
N
ORANGE
D
* Upon printing, this document is considered “uncontrolled”. Please contact Triad Magnetics’ website for the
most current version.
R BROWN
Y
YELLOW A
R
1 Primary and secondary windings are designed to be connected in series or parallel. Windings are not
SCHEMATIC
Y
intended to be used independently.
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
460 Harley Knox Blvd.
Perris, California 92571
Publish Date: August 12, 2014