English
Language : 

N-73A Datasheet, PDF (1/1 Pages) TRIAD MAGNETICS – CHASSIS MOUNT : Isolation
POWER TRANSFORMER
CHASSIS MOUNT : Isolation
N-73A
Electrical Specifications (@25°C)
1. Maximum Power:
150 VA
2. Input Voltage:
115V@50/60Hz
3. Output Voltage:
Series: 230V
Parallel: 115V
4. Full Secondary Load: 0.65 Amps RMS
5. Voltage Regulation: 5 % TYP @ full load to no load
Description:
The N-73A is power transformer for isolating equipment from direct connection to the
power line. It is constructed with nonconcentrically wound coils. The primary and
secondary are wound on separate arbors, then assembled on a laminate core
B
side-by-side separated by insulation. This prevents electrical connection under
normal or overload conditions between the primary and secondary windings.
Safety:
These units are designed with 1500V isolation between winding to winding and
between winding and core. Materials and construction are rated for Class B
A
insulation system.
Dimensions:
A
B
Unit: In inches
C
D
E
3.875 3.281 3.625 2.50 2.750
Weight: 7.0 Lbs.
Mounting Holes: .375 x .187”
Connections: 10.0±1” leads, 0.250±0.062” Skin & Tin
Schematic:
BLK/RED
115V
BLK
0.65 A
E
BLK/YEL
115 V
C
50/60 HZ
BLK/GRN
BLK
WHT
115V
0.65 A
BLK/WHT
INPUT – Between BLK and BLK
OUTPUT: Series: JUMPER BLK/YEL to BLK/GRN. Output between BLK/RED and BLK/WHT,
Parallel: JUMPER BLK/RED to BLK/GRN and BLK/YEL to BLK/WHT. Output between
BLK/RED and BLK/YEL or BLK/GRN and BLK/WHT.
SHIELD: WHT
RoHS Compliance: As of manufacturing date February 2005, all standard products meet the
requirements of 2011/65/EU, known as the RoHS initiative.
D
* Upon printing, this document is considered “uncontrolled”. Please contact Triad Magnetics’ website for
the most current version.
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
460 Harley Knox Blvd.
Perris, California 92571
Publish Date: December 4, 2013