English
Language : 

SDR-480 Datasheet, PDF (1/3 Pages) Mean Well Enterprises Co., Ltd. – 240~480W Miniature with PFC Function
Authorized Distributor: Total Power International, Inc. Toll Free: 877-646-0900(US)PH# (978) 453-7272 www.total-power.com
480W Single Output Industrial DIN RAIL with PFC Function
SDR-480 series
Features :
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.94
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
150% peak load capability
SPECIFICATION
3 years warranty
SEMI
PQ
F47
MODEL
SDR-480-24
SDR-480-48
DC VOLTAGE
24V
48V
RATED CURRENT
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
PEAK CURRENT
30A
15A
PEAK POWER Note.6
720W (3sec.)
OUTPUT RIPPLE & NOISE (max.) Note.2 100mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.2%
LINE REGULATION
0.5%
48 ~ 55V
1.0%
0.5%
LOAD REGULATION
1.0%
1.0%
SETUP, RISE TIME
1500ms, 150ms/230VAC 3000ms, 150ms/115VAC at full load
HOLD UP TIME (Typ.)
14ms/230VAC at full load
VOLTAGE RANGE Note.7 90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.94/230VAC 0.99/115VAC at full load
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
94%
5A/115VAC
40A/115VAC
2.5A/230VAC
80A/230VAC
LEAKAGE CURRENT
<0.8mA / 240VAC
OVERLOAD
PROTECTION OVER VOLTAGE
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
29 ~ 33V
56 ~ 65V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery
OVER TEMPERATURE
105 5 (TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
WORKING TEMP.
Note.5 -25 ~ +70 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 95% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
-40 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
SAFETY & ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
EMC
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
(Note 4) HARMONIC CURRENT
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level,
criteria A , SEMI F47 approved
OTHERS
NOTE
MTBF
112.9Khrs min. MIL-HDBK-217F (25 )
DIMENSION
85.5*125.2*128.5mm (W*H*D)
PACKING
1.6Kg; 8pcs/13.8Kg/0.9CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds peak power max. and the average output power should not exceed the rate power.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.