300W Single Output Battery Charger
PB-300 series
Features :
3 stage charging
AC 115/230VAC selected by switch
Built-in passive PFC function compliance to EN61000-3-2 Class A (option)
Protection: Short circuit / Reverse polarity / Over voltage / Over temperature
Cooling by free air convection
Charger for lead-acid batteries
2 color LED loading indicator
Low cost, High reliability
3 years warranty
(except for 48V)
(P type only)
PB 300 P 12
P:With Passive PFC
N:Without Passive PFC
12:14.4V
24:28.8V
48:57.6V
SPECIFICATION
MODEL
PB-300 -12
PB-300 -24
PB-300 -48
OUTPUT
BOOST CHARGE VOLTAGE 14.4V
FLOAT CHARGE VOLTAGE 13.6V
VOLTAGE ADJUSTABLE RANGE 13 ~ 14.7V
RECOMMENDED BATTERY
60 ~ 200Ah
CAPACITY(AMP HOURS) Note 5
BATTERY TYPE
Open & Sealed Lead Acid
MAX. OUTPUT CURRENT(Typ.) Note 7 20.85A
CONTINUOUS OUTPUT
12.5A
CURRENT (Typ.)
Note 6
28.8V
27.2V
26 ~ 28.8V
30 ~ 100Ah
10.5A
6.25A
57.6V
54.4V
52 ~ 58.6V
15 ~ 50Ah
5.3A
3.2A
INPUT
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
POWER FACTOR (Typ.)
90 ~ 132VAC / 180 ~ 264VAC selected by switch
47 ~ 63Hz
85%
86%
>0.65 (with P type) at 230VAC
127 ~ 187VDC / 254 ~ 370VDC
88%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
6A/115VAC 3A/230VAC
COLD START 60A
LEAKAGE CURRENT
<3.5mA / 240VAC
SHORT CIRCUIT
O/P Built in fuse (FS100) to protect short circuit condition, shut down o/p voltage and can not re-power on
REVERSE POLARITY
By internal fuse
PROTECTION
OVER VOLTAGE
16 ~ 18V
31 ~ 35V
Protection type : Shut down o/p voltage, re-power on to recover
59 ~ 64V
OVER TEMPERATURE
Protection type : Automatically derate charge current until zero
FUNCTION REMOTE CONTROL (CN5) Open: Normal work Short: Stop Charging
WORKING TEMP.
-10 ~ +50 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.05%/ (0 ~ 45 )
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
IEC60335-2-29 CB approved by TUV(except for 48V), UL60950-1 approved
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
Compliance to EN61000-3-2,-3 (only P type)
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
MTBF
115.8Khrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
253*135*48.5mm(L*W*H)
PACKING
1.45Kg; 6pcs/9.7Kg/0.95CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
6. Test condition is at 25 , charging current will change under different temperature.
7. Maximum charging current will be in the range of 90~110% rated output current.
Authorized Distributor: Total Power International, Inc.
Toll Free: 877-646-0900
PH# 978-453-7272
www.total-power.com